The IODDs necessary for the unit's configuration, detailed information about 
process data structure, diagnostic information, parameter addresses and the 
necessary information about required IO-Link hardware and software can be 
found at www.ifm.com.

9  Parameter setting

The parameters of the unit can be set both via the inductive teach button and via 
IO-Link. To be able to use all the functions of the unit, an IO-Link communication 
is required.

9.1  Parameter setting with IO-Link

Using an IO-Link capable parameter setting tool, the following options are 
available:

 -  Reading current process values.
 -  Reading, changing and saving current parameter settings and transmitting 

them to other units of the same type.

 

► Connect the unit via the IO-Link interface to a PC or PLC with suitable 

parameter setting software. 

ifm offers an IO-Link interface for the connection of the sensor via USB 
port.

9.2  Setting parameters via IO-Link

Parameters

Description

Setting range

TI Select

Teach selection

SSC1 / SSC2 / SSC3
default = SSC1

SSC Param SP1 

Switch point 1

-180.0°...179.9°
Steps 0.1°

SSC Config Logic

Switch point logic

0 High active (NO)
1 Low active (NC)

SSC Config Hyst

Switch point hysteresis

0.1°...5°

SSC Tol

Tolerance of the switching 
channel 1

0.1°...15.0°

Pin 5 /gr assignment

Functional assignment for pin 
5 / grey

0 = open / 1 = close / 
2 = seat / -32768 error

Summary of Contents for MVQ101

Page 1: ...Device manual Valve sensor MVQ101 80270936 00 04 2018 UK...

Page 2: ...y may occur The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator Installation electrical connection set up opera...

Page 3: ...h the standard EN 61000 6 4 The unit may cause radio interference in domestic areas The user must take appropriate measures to avoid this interference if necessary 1 2 3 1 Use the two notches at the b...

Page 4: ...pin 4 Communication IO Link Switching output valve position open in SIO mode OUT 2 pin 2 Switching output valve position closed OUT 3 pin 5 Programmable Switching output valve position open Switching...

Page 5: ...ctory red flashing fault in the unit no pulse pick up available teach error switch points SSC1 and SSC2 overlap end position not reached after set time has elapsed unit faulty The LED colours in the t...

Page 6: ...ble Reading current process values Reading changing and saving current parameter settings and transmitting them to other units of the same type Connect the unit via the IO Link interface to a PC or PL...

Page 7: ...lerance and hysteresis can be set separately for each switch point with an additional seal monitoring for SSC2 9 3 2 Parameter setting via inductive teach button The sensor is adjusted using a metal o...

Page 8: ...ch button approx 20 s until the LED ring briefly flashes once 10 Settings 2 2 1 Settings tolerance Set a tolerance range between 0 1 and 15 around the taught set switch point 1 Teach point 2 Tolerance...

Page 9: ...Tolerance width 10 1 Timeout Timeout indicates the maximum duration for closing or opening before the sensor signals a blockage Adjustable time between 0 1 30 s factory setting 30 s In parallel the p...

Page 10: ...Defect of the unit Puck not used Limit value for the timeout exceeded 10 4 Opening closing duration The minimum maximum closing opening duration of the drive can be freely set and monitored The sensor...

Reviews: