7

UK

Power cycles

Number of switching opera-
tions since delivery

0...2147483647

Operating hours

Operating hours counter since 
delivery

0...2147483647

Valve offset

Installation offset of the valve

-180.0°...179.9°
Steps 0.1°

SSC1 and SSC2 
Swap switch points

Swap switch point

Leak warning range

Setting of the leak warning 
range

0.0...15°

9.3  Manual parameter setting
9.3.1  Switch points

The unit has three switch points (SSCs). Two of them can be set via the inductive 
teach button, the third switch point can be configured via IO-Link. Tolerance and 
hysteresis can be set separately for each switch point, with an additional seal 
monitoring for SSC2.

9.3.2  Parameter setting via inductive teach button

The sensor is adjusted using a metal object, e.g. a screwdriver. 

Teach switch point 1 (SSC1) - valve open

 

► Activate teach button until the LED ring flashes yellow. Remove metal tool.

 

> LED ring yellow on, switch point is set.

Teach switch point 2 (SSC2) - valve closed

 

► Change valve position manually.

 

► Activate teach button until the LED ring flashes blue. Remove metal tool.

 

> LED ring blue on, switch point is set.

Swap switch points SSC1 and SSC2

 

► Activate teach button until the LED ring flashes yellow / blue. Remove metal 

tool.

 

> LED ring yellow or blue on, switch point has been swapped.

Summary of Contents for MVQ101

Page 1: ...Device manual Valve sensor MVQ101 80270936 00 04 2018 UK...

Page 2: ...y may occur The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator Installation electrical connection set up opera...

Page 3: ...h the standard EN 61000 6 4 The unit may cause radio interference in domestic areas The user must take appropriate measures to avoid this interference if necessary 1 2 3 1 Use the two notches at the b...

Page 4: ...pin 4 Communication IO Link Switching output valve position open in SIO mode OUT 2 pin 2 Switching output valve position closed OUT 3 pin 5 Programmable Switching output valve position open Switching...

Page 5: ...ctory red flashing fault in the unit no pulse pick up available teach error switch points SSC1 and SSC2 overlap end position not reached after set time has elapsed unit faulty The LED colours in the t...

Page 6: ...ble Reading current process values Reading changing and saving current parameter settings and transmitting them to other units of the same type Connect the unit via the IO Link interface to a PC or PL...

Page 7: ...lerance and hysteresis can be set separately for each switch point with an additional seal monitoring for SSC2 9 3 2 Parameter setting via inductive teach button The sensor is adjusted using a metal o...

Page 8: ...ch button approx 20 s until the LED ring briefly flashes once 10 Settings 2 2 1 Settings tolerance Set a tolerance range between 0 1 and 15 around the taught set switch point 1 Teach point 2 Tolerance...

Page 9: ...Tolerance width 10 1 Timeout Timeout indicates the maximum duration for closing or opening before the sensor signals a blockage Adjustable time between 0 1 30 s factory setting 30 s In parallel the p...

Page 10: ...Defect of the unit Puck not used Limit value for the timeout exceeded 10 4 Opening closing duration The minimum maximum closing opening duration of the drive can be freely set and monitored The sensor...