7
UK
Power cycles
Number of switching opera-
tions since delivery
0...2147483647
Operating hours
Operating hours counter since
delivery
0...2147483647
Valve offset
Installation offset of the valve
-180.0°...179.9°
Steps 0.1°
SSC1 and SSC2
Swap switch points
Swap switch point
Leak warning range
Setting of the leak warning
range
0.0...15°
9.3 Manual parameter setting
9.3.1 Switch points
The unit has three switch points (SSCs). Two of them can be set via the inductive
teach button, the third switch point can be configured via IO-Link. Tolerance and
hysteresis can be set separately for each switch point, with an additional seal
monitoring for SSC2.
9.3.2 Parameter setting via inductive teach button
The sensor is adjusted using a metal object, e.g. a screwdriver.
Teach switch point 1 (SSC1) - valve open
► Activate teach button until the LED ring flashes yellow. Remove metal tool.
> LED ring yellow on, switch point is set.
Teach switch point 2 (SSC2) - valve closed
► Change valve position manually.
► Activate teach button until the LED ring flashes blue. Remove metal tool.
> LED ring blue on, switch point is set.
Swap switch points SSC1 and SSC2
► Activate teach button until the LED ring flashes yellow / blue. Remove metal
tool.
> LED ring yellow or blue on, switch point has been swapped.