Cylinder sensor with IO-Link
MK59xx
9
Window mode
Two switch points (SP1) and (SP2) are manually set or taught. The two switch points delimit a window
area.
Switching back takes place when the hysteresis is exceeded after leaving the window area.
active
inactive
inactive
PDV
0
SP2
SP1
H
H
Fig. 3: Window mode
5.4 Application examples for position monitoring
5.4.1 End position with setting aid
The setting aid can be used to shut down a device or valve prematurely so that the cylinder moves
more smoothly into the end stop.
Cylinder shortly before the end position (e.g. at
80 % of the end position):
LED 1 is on. The output to which SSC1.1 has
been assigned switches.
Cylinder in the end position:
Both LEDs are on, both outputs switch.
5.4.2 Detecting two end positions (short-stroke cylinder)
If the stroke of the cylinder does not exceed the measuring range of the device, both end positions can
be displayed with one device.
Cylinder in end position 1:
LED 1 is on. The output to which SSC1.1 has
been assigned switches.