9 Parameter setting
The parameters are set via the IO-Link interface on pin 4 using the parameter setting software.
Parameters can be set before installation or during operation.
If you change parameters during operation, this will influence the function of the plant.
u
Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.
Requirements for parameter setting via the IO-Link interface:
ü
A suitable parameter setting software, e.g. ifm moneo|configure
ü
The Input Output Device Description (IODD) for the device, see
ü
One IO-Link master
u
Connect the IO-Link master to a parameter setting software.
u
Set the port of the master to the IO-Link operating mode.
u
Connect the device to a free port of the IO-Link master.
w
The unit switches to IO-Link mode.
u
Change parameter settings in the software.
u
Write parameter settings to the unit.
Notes on parameter setting
Ò
Manual of the parameter setting software
When the pneumatic cylinder is changed, it may also be necessary to adapt the device settings.
9.1 Setting switch points
u
Select [Parameter] > [Output configuration] > [oux] and set the switching signal channel for output
OUTx: [SSC1.1] or [SSC1.2].
u
Select [Parameter] > [SSC1.x].
Single point mode:
u
[SSC1.x Config. ]Select [Mode] and set the switch point mode: [Single Point].
u
[SSC1.x Param. ]Select [SP1] and set switch point 1.
u
[SSC1.x Config. ]Select [Hyst] and set the hysteresis.
Two-point mode:
u
[SSC1.x Config. ]Select [Mode] and set the switch point mode: [Two Point].
u
[SSC1.x Param. ]Select [SP1] and set switch point 1.
u
[SSC1.x Param. ]Select [SP2] and set switch point 2.
Window mode:
u
[SSC1.x Config. ]Select [Mode] and set the switch point mode: [Window].
u
[SSC1.x Param. ]Select [SP1] and set switch point 1.
u
[SSC1.x Param. ]Select [SP2] and set switch point 2.
u
[SSC1.x Config. ]Select [Hyst] and set the hysteresis.