Electronic level sensor
LR7009
13
d
d
A
B
C
D
d:
Min. diameter bypass and still pipe
A:
Upper access to the steady area
B:
Upper access to the steady area
C:
Lower access to the steady area
D:
Lower access to the steady area
5.2 Device with coaxial probe
A
B
10 mm
•
No minimum distances to the tank wall and structures in the tank (B)
are required.
u
Minimum distance to the bottom of the tank: 10 mm.
u
The vent hole (A) must not be covered by mounting elements or
similar.
u
Do not install the device in the immediate vicinity of a fill opening. No
water jets must enter into the holes of the coaxial pipe.
Note in case of foam build-up:
u
The vent of the coaxial pipe must be above the maximum level.
u
The lower edge of the coaxial pipe must be below the minimum level.
5.3 Installation of the probe
Rod and coaxial pipe are not included in the scope of delivery. They must be ordered separately:
Ò
Accessories.
5.3.1 Installation of the rod
Fixing of the rod:
6
u
Screw the rod to the device and tighten it.
Tightening torque: 4 Nm
For ease of installation and removal the rod connection can be rotated
without restriction. Even if rotated several times there is no risk of
damage to the device.
In case of high mechanical stress (strong vibration, moving viscous media) it may be necessary to
secure the screw connection, e.g. by a screw retaining compound.