LR3009
Electronic level sensor
30
9.8 Resetting all parameters to factory setting
u
Select [rES], then press [Set] and keep it pressed until [----] is displayed.
u
Briefly press [Mode/Enter].
w
The device reboots and then the factory settings are restored.
Note: on delivery the device is not operational. First, the basic settings must be entered.
[rES]
9.9 Changing basic settings
Changing the basic settings is required after changes to the probe or to the application area.
9.9.1 Re-entering probe length
u
Change to menu level 2
u
Select [LEnG] and set probe length L. Step increment: 0.5 cm
Remarks on the determination of the probe length
:
u
Observe the notes on single probes or coaxial probes.
u
Briefly press [Mode/Enter].
Note: after changing the probe length, the values for OFS and the switching limits must also be re-
viewed / re-entered.
[LEnG]
9.9.2 Setting to another medium
u
Select [MEdI] and set the value:
• [HIGH] for water and water-based media.
• [LOW] for oils and oil-based media.
Note: in case of doubt, carry out an application test to ensure the setting which is best for your medi-
um.
[MEdI]
9.9.3 Changing the value of the type of probe used
u
Select [Prob] and set the value:
• [rod] for single probe.
• [COAX] for coaxial probe.
The detection of water and water-based media is possible with the single probe as well as with the co-
axial probe.
The detection of oils and oil-based media is only possible with the coaxial probe. Therefore, the pa-
rameter [Prob] is not available in case of the setting [MEdI] = [LOW] (the value [COAX] is preset).
[Prob]