10.3 Commands
10.3.1 Adjustment of the sensor
Command
Description
Adjust empty tank
Carries out the empty adjustment of the sensor�
The environment is suppressed�
Adjust full tank
Carries out the full adjustment of the sensor�
The environment is suppressed�
Start dynamic tank
adjustment
Starts the dynamic adjustment� The level must be within
the measuring range, but at least 4 sensor elements
below the upper limit of the detection range�
Stop dynamic tank
adjustment
Stops the dynamic adjustment and calculates the
adjustment values�
Cancel dynamic tank
adjustment
Aborts the dynamic adjustment without calculating
adjustment values�
Reset tank adjustments
Resets all application adjustments of the sensor�
10.3.2 Setting of the switch points
Besides setting of the switch points via IO-Link
switch-off point can be set to the currently provided process value�
Command
Description
Adjust SPx
Sets the switch point of OUTx to the current process value�
Adjust rPx
Sets the switch-off point of OUTx to the current process value�
During teaching of the switch-off point, it is checked whether the switch-off
point to be taught is below the set switch point� If this is not the case, the
teach will be refused�
During teaching of the switch point, the switch-off point will automatically
be adjusted by the sensor so that the hysteresis between switch point and
switch-off point that was set before the teach is maintained� The switch
point and the switch-off point must be within the value range
� If
this is not the case, the switch-off point and the switch point will be limited
by the value range and the hysteresis will be reduced accordingly�