UK
Operating instructions FX460
33
RESULT=0
Display value equal to 0 (standstill after standstill time), e�g� standstill
monitoring� (Only in SPEED and PROCESS TIME operating modes�)
RESULT≥ PRES->0
Set display to 0� (Only in the TIMER or COUNTER operating modes)�
If the display value is greater than or equal to preselection 1, the
display value is set to zero� If BATCH MODE is activated and the
selected source is MEASUREM� RESULT, COUNTER A or COUNTER
B, the batch counter is incremented / decremented each time it is reset
to 0�
RESULT≤ 0->SET
Set display to preselection 1� (Only in the TIMER or COUNTER
operating modes)�
If the display value is smaller than or equal to 0, the display value is set
to preselection 1� If BATCH MODE is activated and the selected source
is MEASUREM� RESULT, COUNTER A or COUNTER B, the batch
counter is incremented / decremented each time it is set to preselection
1�
RES≥PRES-TRAIL
Tracking preset 1:
Display value greater or equal to preselection 2 – preselection 1
Preselection 1 is the tracking preset of preselection 2�
HYSTERESIS 1
Hysteresis to define the switch-off point for the switching condition of preselection 1
0
No switching hysteresis
…
99999
Switching hysteresis of 99999
PULSE TIME 1 (S)
Duration of the fleeting pulse (in seconds) for the switching condition of preselection 1
0�000
No fleeting pulse (static signal)
…
60�000
Pulse duration of 60 seconds
OUTPUT TARGET 1
Assignment of an output for the switching condition of preselection 1�
If several switching conditions are assigned to one single output, this output is active as soon as one of the
switching conditions is met�
NO
No assignment
CTRL OUT 1
Assignment of the switching condition to Ctrl� Out 1
CTRL OUT 2
Assignment of the switching condition to Ctrl� Out 2
CTRL OUT 3
Assignment of the switching condition to Ctrl� Out 3
CTRL OUT 4