Operating instructions 

Flow monitors

SI6000 

SI6100 

SI6200

706053/00

 

06/201

1

UK

Summary of Contents for efector300 SI6000

Page 1: ...Operating instructions Flow monitors SI6000 SI6100 SI6200 706053 00 06 2011 UK ...

Page 2: ... 6 4 Electrical connection 8 5 Operating and display elements 8 6 Set up and settings for water 9 6 1 Change the switch point optional 9 6 2 High flow adjustment optional 10 7 Additional settings optional 10 7 1 Low flow adjustment 10 7 2 Configure the switching output 10 7 3 Restore the factory setting reset 11 7 4 Lock unlock the unit 11 8 Error during adjustment 11 9 Operation 12 10 Maintenance...

Page 3: ...ead to malfunctions of the unit or to un wanted effects in your application That is why installation electrical connection set up operation and mainte nance of the unit must only be carried out by qualified personnel authorised by the machine operator For the scope of validity cULus The device shall be supplied from an isolating transformer having a secondary Listed fuse rated as noted in the foll...

Page 4: ...en applies output open if medium is flowing If the flow speed increases the switching status changes when the switch point is reached If the flow speed falls again the switching status changes if the value SP minus hysteresis is reached The hysteresis changes with the flow speed and it is essentially influenced by the set monitoring range It is 2 5 cm s for the setting 5 100 cm s factory setting i...

Page 5: ...ion General The sensor tip is to be completely surrounded by the medium Insertion depth of the sensor minimum 12 mm Recommended For horizontal pipes mounting from the side For vertical pipes mounting in the rising pipe Conditional Horizontal pipe mounting from the bottom if the pipe is free from build up Horizontal pipe mounting from the top if the pipe is completely filled with medium To avoid Th...

Page 6: ... medium This affects the function of the unit Recommendation Adhere to the distances between sensor and sources of interference D pipe diameter S sources of interference 3 3 Mounting operation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installation G grease ...

Page 7: ...y Make sure that the O ring C is correctly positioned Screw the unit into the adapter until it is hand tight Avoid mechanical influence on the sealing areas Clamp unit and adapter into a clamping device E The sealing areas F must not be damaged Tighten the unit slightly using a spanner until you can feel the end stop this corresponds to a maximum tightening torque of 25 Nm NOTE Further tight ening...

Page 8: ...PELV Disconnect power Connect the unit as follows Core colours of ifm sockets 1 BN brown 3 BU blue 4 BK black 5 Operating and display elements 1 Operation display The green LEDs indicate the current flow the LEDs 0 to 9 represent the range between no flow and maximum flow A lighting LED indicates the position of the switch point orange output closed red output open 2 3 Setting buttons for adjustme...

Page 9: ... 6 2 3 Your normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 6 2 You can restore the factory setting any time 7 3 6 1 Change the switch point optional For the factory setting the switch point is at LED 7 A change makes sense if the display shows example 2 the flow fluctuates much or pulsates if a faster response time of the unit is requested ...

Page 10: ... you should additionally adapt the unit to the minimum flow Note The following adjustment must only be carried out after the high flow adjust ment Let the minimum flow circulate in the installation or ensure flow standstill Press the pushbutton and keep it pressed LED 0 lights after approx 5 s it flashes Release the pushbutton The unit adopts the new value and passes into the operating mode 7 2 Co...

Page 11: ...multaneously for at least 10 s in the operating mode The indication goes out the unit locks or unlocks On delivery unlocked 8 Error during adjustment If no adjustment is possible all LEDs flash red The unit then passes into the operating mode with unchanged values Possible cause aid Error during installation Read chapter 3 Installation Check whether all requirements have been met The difference be...

Page 12: ...he representation range LED 0 flashes current flow far below the represen tation range Interference indicators Short circuit at the switching output The operating indicator and red LEDs light alternately If the short circuit has been rectified the unit im mediately passes into the normal operating state The current operating state is displayed Display OFF no LED lights Operating voltage too low 19...

Page 13: ...13 UK 11 Scale drawing SI6000 1 LED bar display 2 set button 3 Aseptoflex thread ...

Page 14: ...14 SI6100 1 LED bar display 2 set button 3 Aseptoflex thread ...

Page 15: ...15 UK SI6200 1 LED bar display 2 set button 3 Aseptoflex thread ...

Page 16: ...cm s 2 102 Hysteresis cm s 2 52 Repeatability cm s 1 52 Temperature drift cm s x 1 K 0 13 Response time s 1 10 Pressure resistance bar 30 Operating temperature C 25 60 Protection rating IP 67 IP 69K Protection class III Shock resistance g 50 DIN IEC 68 2 27 11 ms Vibration resistance g 20 DIN IEC 68 2 6 55 2000 Hz Housing materials stainless steel 316L 1 4404 PC Makrolon PBT GF 20 EPDM X Santopren...

Page 17: ...17 UK More information at www ifm com ...