30
Setting of the display
7 options can be selected:
d1
= update of the measured value every 50 ms
d2
= update of the measured value every 200 ms
d3
= update of the measured value every 600 ms
The update interval only refers to the display. It has no effect on
the outputs.
rd1
,
rd2, rd3
= display as d1, d2, d3; but rotated 180°.
OFF
= In the Run mode the display of the measured value is
deactivated. If one of the buttons is pressed, the current measu-
red value is displayed for 15 s. Another press of the Mode/Enter
button opens the Display mode. The LEDs remain active even if
the display is deactivated.
Reset to factory settings
- Press the "Mode/Enter" pushbutton until
rES
is displayed.
- Press the "Set" pushbutton and keep it pressed until "
- - - -
"
is displayed.
- Then press the "Mode/Enter" pushbutton briefly.
All modified parameter settings will be reset. Therefore it makes
sense to note down your own settings before (
→
table on page
52).
Damping for the analogue output (OU2)
Pressure peaks of short duration or high frequency can be
filtered out.
dAA-value = response time between pressure change and
change of the switching status in seconds (s).
• Setting range: 0,1 ... 100 s in steps of 0.1 s
(0.1 = dAA is not active).