Min-Max memory for system pressure
• HI: displays the highest measured pressure
• LO: displays the lowest measured pressure
Erase the memory:
- Press the "Mode/Enter" button until
HI
or
LO
is displayed.
- Press the "Set" button and keep it pressed until “
- - - -
” is
displayed.
- Then press the "Mode/Enter" button briefly.
Delay time for the switching output
dS1
= switch-on delay;
dr1
= switch-off delay
The output does not immediately change its switching status
when the switching condition is met but when the delay time
has elapsed. If the switching condition is no longer met when
the delay time has elapsed, the switching state of the output
does not change.
• Setting range: 0 / 0.1 ... 50 s adjustable in steps of 0.1 s
(0 = delay time not active),
• Indicated in seconds.
Output polarity (output 1)
2 options can be selected:
-
PnP
= positive switching
-
nPn
= negative switching
Damping for the switching output (OU1)
Pressure peaks of short duration or high frequency can be
filtered out.
dAP-value = response time between pressure change and c
hange of the switching status in seconds (s).
• Setting range: 0.1 ... 100 s in steps of 0.1 s
(0.1 = dAP is not active).
Correlation between switching frequency and dAP: f
max
=
Damping also affects the display.
2
×
dAP
1
Calibration offset
The internal measured value (operating value of the sensor) is
offset against the real measured value.
• Setting range: -5 ... +5% of the value of the measuring range
(with scaling as factory setting (ASP = 0% and AEP = 100%),
• in steps of 0.1% of the value of the measuring range.
COF can also be set by means of the teaching process (
→
tCOF
).