Scaling the measuring range
• With the parameter "Analogue start point" (
ASP
) the measured
value at which the output signal is 4 mA is defined.
• With the parameter "Analogue end point" (
AEP
) the measured
value at which the output signal is 20 mA is defined.
• Minimum distance between ASP and AEP = 25 % of the span (scal-
ing factor 4).
The output signal is between 4 and 20 mA in the set measuring range.
It is also indicated:
• System pressure above the measuring range: output signal > 20 mA.
• System pressure below the measuring range: output signal drops to
max. 3.2 mA (depending on the scaling).
21
ENGLISH
4
Technical information / Functioning / Parameters
I [mA]
4
20
+4 (AEP)
0 (ASP)
-1
I [mA]
P [bar]
4
20
AEP
ASP
-1
0
+4
0
0
P [bar]
Factory setting
Measuring range scaled