Mounting of the adapter
Step 1
Screw the sensor into the
adapter.
Step 2
Clamp sensor and adapter into a
clamping device (C). The sealing
chamfers (D) must not be dam-
aged. Tighten the sensor with a
spanner.
Tightening torque: 20 Nm.
Electrical connection
The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Operating voltage "supply class 2" to cULus / to EN50178, SELV,
PELV.
Disconnect power before connecting the unit as follows:
15
2
ENGLISH
Core colours of ifm sockets: 1 = BN (brown), 2 = WH (white),3 = BU (blue),
4 = BK (black); n.c. = not connected.
L+
3
4
2
1
BU
BK
BN
WH
L-
n.c.
n.c.
3
1
4
2
L+
3
4
2
1
BU
BK
BN
WH
L-
n.c.
Connector view
(sensor)
2 wire connection
3 wire connection