Adjustable parameters
19
4
ENGLISH
Technical information / Functioning / Parameters
Analogue start point
Measured value at which 4 mA is provided.
Analogue end point
Measured value at which 20 mA is provided.
Minimum distance between ASP and AEP = 25% of the span.
in steps of
ASP
Setting range:
AEP
bar
0.01
-0.99 ... 1.00
0.26 ... 4.00
-14.4 ... 14.5
3.7 ... 58.0
-99 ... 100
26 ... 400
PSI
0.1
kPa
1
Calibration offset
The internal measured value (operating value of the sensor) is
offset against the real measured value.
•Ssetting range: -5 ... +5% of the value of the span
(with scaling as factory setting (ASP = 0 bar and AEP = 4 bar),
• in steps of 0.1% of the value of the span.
Calibration reset
Resets the calibration set by COF.
Min-Max memory for system pressure
• HI: displays the highest measured pressure.
• LO: displays the lowest measured pressure.
Damping for the analog output
Pressure peaks of short duration or high frequency can be filtered
out.
dAA-value = response time between pressure change and
change of the switching status in milliseconds (ms).
• setting range: 0 (= dAA is not active) / 0.1 s / 0.5 s / 2 s.
Display unit
The measured values and values for ASP / AEP can be indicated
in the following units:
bar, PSI
,
kPA.
Select the
display unit before setting the
limits for the analo-
gue output signal (ASP, AEP). This avoids rounding errors genera-
ted internally during the conversion of the units and enables
exact setting of the limits for the analog output signal.
ASP
AEP
HI
LO
COF
CAr
dAA
Uni