DP module 12: Extended command channel
Module 12, extended command 96dec (60hex):
save data non-volatilely in the flash memory of the controllere
9-67
9.35
Module 12, extended command 96
dec
(60
hex
):
save data non-volatilely in the flash memory of the controllere
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R
R
R
user ID
command number = 60
hex
= 96
dec
2
reserved = 0
reserved = 0
3
0 area
number
4…18
not used
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0965
09 = user ID changes e.g. to 9,
60 = command number 96
2 0000
reserved
3 0002
area number:
02 = save the configuration of AS-i master 1 non-volatilely
03 = save the configuration of AS-i master 2 non-volatilely
Response from controllere (gateway)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0 B=0 R
reflected user ID
reflected command number = 60
hex
2
reserved = 0
reserved = 0
3
0
reflected area number
4…18
not changed
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0960
09 = reflected user ID changes e.g. to 9,
60 = reflected command number 96
2 0000
reserved
3 0002
reflected area number
02 = save the configuration of AS-i master 1 non-volatilely
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...