84BFaulty AS-i messages on the master
13-20
13.11
Faulty AS-i messages on the master
A message error means that the expected response message from a slave is not
received within a defined time or that the signal sequences in the response mes-
sage of the AS-i master cannot be interpreted.
Examples:
•
The AS-i line is asymmetrically operated due to an electric fault (earth fault on
one side). The AS-i signal is no longer clearly recognisable.
•
The electrical AS-i connection to an AS-i slave is not ok.
•
Interference by the electric environment of the AS-i network (EMC) affects the
AS-i message traffic.
Here you can not see in detail when every individual fault occurred.
→
The error counter is reset...
•
when the unit is switched off and on again
•
with the function "Reset error counter",
→
M
M
E
E
N
N
U
U
0
U
U
S
S
E
E
R
R
1.
►
Press the [
MENU
] button
Quick Setup
PLC Setup
Slave Lists
O
O
K
K
1
▲
▼
E
E
S
S
C
C
2.
►
Press [
▼
] to scroll to "Diagnostics"
Slave Lists
Address Slave
Diagnostics
O
O
K
K
1
▲
▼
E
E
S
S
C
C
3.
►
Press [
OK
] to select "Diagnostics"