Connection of sensors (24 V DC):
To guarantee safe functioning, signal cables and load cables should be laid sepa-
rately. Use screened cable if necessary.
5. Programming
Locking/unlocking
The unit can be locked to prevent unwanted adjustment of the set parameters.
Select parameter P00, enter value 1 and acknowledge with the
button.
For unlocking:
- Press the
button for a short time.
will be shown in the display.
- Now press the
,
and
buttons one after the other within 5s.
P
P
13
DIGITAL DISPLAY
DA 340
ENGLISH
3
5
6
0-1 V
3
5
7
0-10 V
3
5
6
9
0/4-20mA
5
6
9
4-20mA
range 0 - 1 V
range 0 - 10 V
range 0/4 - 20 mA
range 4 - 20 mA
3
5
8
6
0-xx V
Rx
freely definable voltage range 0 - xx V
The maximum value of the voltage range can be assigned by an
external resistor between terminals 8 and 6.
Calculation of the resistance value:
R [k
Ω
Ω
] = (U [V] x 25) - 25
U
max
= 120 V!
1
Changeover to the
programming mode
Press the
button for a short time.
is shown in the display.
P
2
Selection
of the
parameter to
be changed
Press the
or
button until the requested parameter is shown
in the display.*
Press the
button.
The current parameter value is shown
in the display.
3
Setting of
parameter
If no button is pressed any more, the unit will return to the operating mode after 8s. The changed
parameter values will become active.**
Press the
or
button until the requested parameter value
is shown in the display. *
Press the
button.
The next parameter is shown in the display.
Continue with step 2.
*Setting step by step by pressing the button once or continuously by pressing it permanently.
Quick run: pressing the
(or
) and
buttons once at the same time.
**Active termination of the programming mode: Select parameter P85, enter value 1 and
acknowledge with the
button.
P