6. Adjustable parameters

14

DIGITAL DISPLAY

DA 340

Parameter

Parameter value

P00

keyboard locking

0 = keyboard locking inactive
1 = keyboard locking active

P01

operating mode:

- level of the input signal and

- display mode proportional 

reciprocal

1 = 0 ... 1 V; 0 ... xx V / proportional display
2 = 0 ... 10 V / proportional display
3 = 0 ... 20 mA / proportional display
4 = 4 ... 20 mA / proportional display
5 = 0 ... 1 V; 0 ... xx V / reciprocal display
6 = 0 ... 10 V / reciprocal display
7 = 0 ... 20 mA / reciprocal display
8 = 4 ... 20 mA / reciprocal display

P02

scaling factor:
numerical value to be displayed with the
maximum of the input signal

range of values: 1 ... 999 999

P07

decimal point of the display

range of values: 0 ... 5
0 = none, 5 = 5 places after the point

P10

preset 1 (minimum value):
displayed value at which OUT 1 (min.) 
is to switch

range of values: 0 ... 999 999

P11

preset 2 (max.):
displayed value at which OUT 2 (max.) 
is to switch

range of values: 0 ... 999 999

P12

switching performance of the outputs 
OUT 1 (min.) and OUT 2 (max.)

1 = both outputs switch when the relevant preset 

value has been exceeded

2 = output (min.) switches when the relevant 

preset value has not been reached, output 
(max.) switches when the relevant preset value
has been exceeded

P17

offset
numerical value which is added to the 
current displayed value

range of values: -99999 ... +99999

P16

linearisation
free definition of a linearisation graph for 
the displayed values

0 = linearisation inactive
1 = linearisation active

P18

fleeting time for OUT 1 (min.)
The output changes its switching status when
the limit value has been exceeded or has not
been reached for the length of the set fleet-
ing time. Then it returns to the initial status.

range of values: 0.00 ... 9.99s
(0.00 = fleeting time not active, output is switched
statically)

P19

fleeting time for OUT 2 (max.)

range of values: 0.00 ... 9.99s; (0,00: see P18)

P20

fleeting time for OUT 3 (display 0)

range of values: 0.00 ... 9.99s; (0.00: see P18)

P23

function of the 

key in the operating

mode

0 = no function
5 = delete min./max. memory

P24

function of the 

key in the operating

mode

0 = no function
5 = delete min./max. memory

P25

function of the 

key in the operating

mode

0 = no function
5 = delete min./max. memory

P26

read min./max. memory

display of the current minimum value

P27

read max./min. memory

display of the current maximum value

P29

start-up delay for OUT 1 (min.)
The output switches after the start-up delay
has elapsed.The time starts with the applica-
tion of the operating voltage or after reset.

range of values:
0s = start-up delay not active
0.01 ... 99.98s start-up delay active
99.99s = output "min." remains locked until the
displayed value falls below the preset min. value
for the first time

Summary of Contents for Ecomat 200 DA 340

Page 1: ...Betriebsanleitung Operating instructions Notice d emploi Digital Display Digital display Afficheur numérique DA 340 P K1 K2 K3 K4 DEUTSCH ENGLISH FRANÇAIS R Sachnr 701394 01 01 2001 ...

Page 2: ...te 4 4 Elektrischer Anschluß Seite 4 Anschluß von Sensoren Seite 5 5 Programmieren Seite 5 6 Einstellbare Parameter Seite 6 7 Konfigurieren der Anzeige Seite 7 8 Konfigurieren der Ausgänge Seite 8 9 Weitere Funktionen Seite 9 10 Betrieb Seite 9 11 Technische Daten Seite 9 2 DIGITAL DISPLAY DA 340 ...

Page 3: ...t Skalierung Dezimalpunkt Offset Linearisierung Mittelwertbildung Konfiguration der Ausgänge Vorwahl Schaltfunktion Wischen Anlaufüberbrückung 2 Bedien und Anzeigeelemente P K1 K2 K3 K4 1 2 3 4 5 6 1 Programmiertaste Übergang in den Programmiermodus 2 3 Einstelltasten aufwärts abwärts Wahl der Parameteradresse und des Parameterwerts Einstellung schrittweise durch Einzeldruck oder kontinuierlich du...

Page 4: ...r steckbar Klemmenbelegung 4 DIGITAL DISPLAY DA 340 X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 GND 24V DC IN GND 5 V DC OUT 24V DC OUT 0 1V L 230 V AC L 115 V AC N 0 10V 0 xxV 0 4 20 mA n c OUT 1 min OUT 2 max OUT 3 display 0 24V Com X2 n c n c n c Sensorversorgung Versorgungs spannung DC Signaleingänge Schaltausgänge Versorgungs spannung AC Klemmen dürfen nicht belegt werden Klemmen 1 17 sind p...

Page 5: ...festlegen Berechnung des Widerstandswerts R kΩ Ω U V x 25 25 Umax 120 V 1 Wechsel in den Programmiermodus Drücken Sie kurz die Taste Im Display erscheint P 2 Anwahl des Parameters der verändert werden soll Drücken Sie die Taste oder bis der gewünschte Parameter im Display erscheint Drücken Sie die Taste Im Display erscheint der aktuelle Parameterwert 3 Einstellen des Parameterwerts Wird keine Tast...

Page 6: ...d Wertebereich 99999 99999 P16 Linearisierung Vorgeben einer frei definierten Linearisierungskurve für die Anzeigewerte 0 Linearisierung AUS 1 Linearisierung EIN P18 Wischzeit für OUT 1 Min Der Ausgang ändert seinen Schaltzustand bei Über bzw Unterschreiten des Grenzwer tes für die Dauer der eingestellten Wischzeit Danach geht er in den Ausgangszustand zurück Wertebereich 0 00 9 99s 0 00 Wischzeit...

Page 7: ...lle Applikationen Sie ersetzen dabei 10 Werte der intern berechneten Kurve x Werte durch 10 frei definierte Anzeigewer te y Werte Das Gerät verbindet die Punkte zwischen den y Werten durch Gera den und erstellt damit eine frei definierte Kurve der Anzeigewerte Gehen Sie fol gendermaßen vor a Parametrieren Sie die Anzeige wie oben Punkt 1 bis 3 b Geben Sie bis zu 10 x Werte ein Parameter P41 bis P5...

Page 8: ...1 bis P60 ein 4 Setzen Sie dann Parameter P16 auf den Wert 1 8 Konfigurieren der Ausgänge Stellen Sie folgende Parameter ein Vorwahl 1 Grenzwert bei dem OUT 1 sein Schaltverhalten ändert Parameter P10 Vorwahl 2 Grenzwert bei dem OUT 2 sein Schaltverhalten ändert Parameter P11 Schaltfunktion von OUT 1 und OUT 2 Schalten bei Überschreiten Unterschreiten der Vorwahl Parameter P12 Wischzeit Impulsverl...

Page 9: ...stendruck 10 Betrieb Prüfen Sie nach Montage Verdrahtung und Programmierung ob das Gerät sicher funktioniert Bei sachgemäßem Betrieb sind keine Maßnahmen für Wartung und Instandhaltung notwendig 11 Technische Daten Nennspannung AC V Nennspannung DC V Leistungsaufnahme VA Stromaufnahme mA Schutzart Gehäusefront Umgebungstemperatur C Maße mm Schalttafel Ausschnitt mm Analogeingänge Hilfsspannung V S...

Page 10: ...e 12 4 Electrical connection page 12 Connection of sensors page 13 5 Programming page 13 6 Adjustable parameters page 14 7 Configuration of the display page 15 8 Configuration of the outputs page 16 9 Additional functions page 17 10 Operation page 17 11 Technical data page 17 10 DIGITAL DISPLAY DA 340 ...

Page 11: ...mode scaling decimal point offset linearisation mean value genera tion configuration of the outputs preset switching function fleeting start up delay 2 Operating and indicating elements 11 DIGITAL DISPLAY DA 340 ENGLISH P K1 K2 K3 K4 1 2 3 4 5 6 1 Programming button changeover to the programming mode 2 3 Setting buttons up down selection of the parameter address and the parameter value Setting ste...

Page 12: ...tection Connection 12 DIGITAL DISPLAY DA 340 X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 GND 24V DC IN GND 5 V DC OUT 24V DC OUT 0 1V L 230 V AC L 115 V AC N 0 10V 0 xxV 0 4 20 mA n c OUT 1 min OUT 2 max OUT 3 display 0 24V Com X2 n c n c n c sensor supply DC supply signal inputs outputs AC supply terminals must not be used The terminals 1 to 17 are electrically isolated from the mains ...

Page 13: ... terminals 8 and 6 Calculation of the resistance value R kΩ Ω U V x 25 25 Umax 120 V 1 Changeover to the programming mode Press the button for a short time is shown in the display P 2 Selection of the parameter to be changed Press the or button until the requested parameter is shown in the display Press the button The current parameter value is shown in the display 3 Setting of parameter If no but...

Page 14: ...hich is added to the current displayed value range of values 99999 99999 P16 linearisation free definition of a linearisation graph for the displayed values 0 linearisation inactive 1 linearisation active P18 fleeting time for OUT 1 min The output changes its switching status when the limit value has been exceeded or has not been reached for the length of the set fleet ing time Then it returns to ...

Page 15: ...place 10 values of the graph calculated internally x values by 10 freely defined displayed values y values The unit links the points between the y values by straight lines and thus creates a freely defined graph of the displayed values Proceed as follows a Parameter setting of the display as described above 1 to 3 b Enter up to 10 x values parameters P41 to P50 The first value in P41 should be 0 t...

Page 16: ...Then set parameter P16 to the value 1 8 Configuration of the outputs Set the following parameters Preset 1 limit value at which OUT 1 changes its switching performance parameter P10 Preset 2 limit value at which OUT 2 changes its switching performance parameter P11 Switching function of OUT 1 and OUT 2 switch when the preset has been exceeded not reached parameter P12 Fleeting time pulse stretchin...

Page 17: ...ation After mounting wiring and programming check the safe functioning of the unit In case of correct use no maintenance measures are necessary 11 Technical data 17 DIGITAL DISPLAY DA 340 ENGLISH Nominal voltage AC V Nominal voltage DC V Power consumption VA Current consumption mA Protection housing front Operating temperature C Dimensions mm Control panel cutout mm Analog inputs Auxiliary voltage...

Page 18: ...4 Raccordement électrique page 20 Raccordement des capteurs page 21 5 Programmation page 21 6 Paramètres réglables page 22 7 Configuration de l affichage page 23 8 Configuration des sorties page 24 9 Fonctions supplémentaires page 25 10 Fonctionnement page 25 11 Données techniques page 25 18 AFFICHEUR NUMÉRIQUE DA 340 ...

Page 19: ... une valeur moyenne configuration des sorties présélection fonction de commutation impulsions de passage temporisation de démarrage 2 Eléments de service et d indication 19 AFFICHEUR NUMÉRIQUE DA 340 FRANÇAIS P K1 K2 K3 K4 1 2 3 4 5 6 1 bouton de programmation passage dans le mode programmation 2 3 bouton de réglage haut bas sélection de l adresse de paramètre et de la valeur de paramètre réglage ...

Page 20: ...de branchement 20 AFFICHEUR NUMÉRIQUE DA 340 X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 GND 24V DC IN GND 5 V DC OUT 24V DC OUT 0 1V L 230 V AC L 115 V AC N 0 10V 0 xxV 0 4 20 mA n c OUT 1 min OUT 2 max OUT 3 display 0 24V Com X2 n c n c n c alimentation du capteur alimentation DC du boîtier signaux d entrée sorties alimentation AC du boîtier ces bornes ne doivent pas être utilisées Les broches ...

Page 21: ...tre les bornes 8 et 6 Calcul de la valeur de la résistance R kΩ Ω U V x 25 25 Umax 120 V 1 passage dans le mode programmation Appuyer sur le bouton brièvement est affiché P 2 sélection du paramètre à changer Appuyer sur le bouton ou jusqu à ce que le paramètre désiré soit affiché Appuyer sur le bouton La valeur de paramètre actuelle est affichée 3 réglage de la valeur de paramètre Si aucun bouton ...

Page 22: ...me de valeurs 99999 99999 P16 linéarisation définition d un graphe de linéarisation à défi nir au libre choix pour les valeurs d affichage 0 linéarisation non active 1 linéarisation active P18 durée des impulsions pour OUT 1 mini La sortie change son état de commutation si la valeur est supérieure ou inférieure à la valeur limite pendant la durée des impulsions réglée Ensuite elle rentre dans son ...

Page 23: ...ation à définir au libre choix afin de compenser des erreurs de mesure des capteurs ou pour des applications spéciales On remplace 10 valeurs du graphe calculé inter nement valeurs x par 10 valeurs d affichage définies au libre choix valeurs y L appareil lie les points entre les valeurs y par des lignes droites et crée ainsi un graphe défini au libre choix des valeurs d affichage Procéder comme su...

Page 24: ...u X1 à X9 paramètres P41 à P49 Entrer la valeur de mesure pour la cuve pleine en paramètre P50 3 Ensuite entrer les valeurs d affichage désirées quantité de la matière en paramètres P51 à P60 4 Ensuite mettre paramètre P16 à la valeur 1 8 Configuration des sorties Régler les paramètres suivants Présélection 1 valeur limite sur laquelle OUT 1 change son comportement de com mutation paramètre P10 Pr...

Page 25: ...ramètres P23 P24 ou P25 et effacer la mémoire pendant le fonctionnement en appuyant sur le bouton 10 Fonctionnement Après l installation le câblage et la programmation vérifier le bon fonctionnement de l appareil En cas de bonne utilisation l appareil nécessite aucun entretien 11 Données techniques 25 AFFICHEUR NUMÉRIQUE DA 340 FRANÇAIS Tension nominale AC V Tension nominale DC V Puissance absorbé...

Page 26: ...Notizen Notes 26 AFFICHEUR NUMÉRIQUE DA 340 ...

Page 27: ...Technische Änderungen behalten wir uns ohne vorherige Ankündigung vor Papier chlorfrei gebleicht ...

Reviews: