4.3 Laying of supply and signal cables
Basically all supply and signal cables are to be laid separately.
Connect supply and ground cables to the controller and the sensors/actua-
tors respectively via a common star point
The linking of connections in the plug is not permitted and can impact
safety of persons and machinery.
4.4 Frequency inputs
Operate frequency inputs with screened cables, so that useful signals are
not affected by external interference.