4.3 Laying of supply and signal cables

Basically all supply and signal cables are to be laid separately.
Connect supply and ground cables to the controller and the sensors/actua-
tors respectively via a common star point
The linking of connections in the plug is not permitted and can impact
safety of persons and machinery.

4.4 Frequency inputs

Operate frequency inputs with screened cables, so that useful signals are
not affected by external interference.

C

ABINET

C

ONTROLLER

CR0303

7

UK

sensor

sensor

load

supply

OUT 00

OUT 01

controller

VBB

S

GND

IN nn

load

VBB

O 01

OUT 04

OUT 05

VBB

O 02

VBB

S OUT

IN nn

VBB

S OUT

IN nn

sensor

P/N1

VBB

STAB (5/10 V)

load

load

= not permitted

Explanation of the abbreviations:

VBB

O

= supply outputs

VBB

S

= supply controller

VBB

S OUT

= supply sensors

VBB

STAB

= supply sensors stabilised 5/10 V DC

Summary of Contents for Ecomat 100 CR0303

Page 1: ...Device manual Mobile controller CabinetController CR0303 UK 7390608 01 03 2015...

Page 2: ...quency inputs page 7 5 Setup 5 1 Programming page 8 6 Technical data data sheets 1 5 Dimensions mechanics electronics page 9 Operating and indicating elements page 10 Rotary switch coding page 10 Oper...

Page 3: ...ELV circuit of the device must al so comply with the SELV criteria safety extra low voltage safe electrical separa tion from other electric circuits If the supplied SELV voltage has an external connec...

Page 4: ...master or intelligent I O module The user is responsible for the safe function of the application programs which he created himself If necessary he must additionally carry out an ap proval test by cor...

Page 5: ...Nm Mounting position any Hole dimensions see back of the controller or Technical data page 9 3 3 Cooling As the internal heating of the electronics is conducted away via the housing en sure sufficien...

Page 6: ...er the individual electric circuits must be protected www ifm com CABINETCONTROLLER CR0303 6 Designation Potential Plug pin Fuse Supply voltage module VBBS P N1 01 max 2 A T Supply voltage OUT00 03 VB...

Page 7: ...ns and machinery 4 4 Frequency inputs Operate frequency inputs with screened cables so that useful signals are not affected by external interference CABINETCONTROLLER CR0303 7 UK sensor sensor load su...

Page 8: ...manual CoDeSys V2 3 alternatively online help CoDeSys If the system manual R360 is not available please contact one of the ifm branch offices overleaf for your free copy System manual R360 English or...

Page 9: ...junior timer contacts inputs outputs 2 x 10 pole 3 x 18 pole operating voltage CAN bus 1 x 6 pole programming TEST 1 x 6 pole Weight 0 68 kg Operation storage temperature 40 85 C Protection rating IP...

Page 10: ...n protocol predefined ifm protocol INTELHEX or free protocol Controller CMOS microcontroller 16 bits C167C 40 MHz Memory program memory 576 Kbytes flash data memory 80 Kbytes SRAM 32 Kbytes flash 2 Kb...

Page 11: ...50 Hz Digital inputs for negative sensor signals switch on level 0 2 UB switch off level 0 5 UB input resistance 3 17 k input frequency 50 Hz Analogue inputs A Voltage inputs X11 01 04 07 10 input vo...

Page 12: ...utput for the sensor supply X20 14 voltage 5 10 V DC can be selected switched off or read back The 10 V output requires at least 13 V supply voltage to work current 400 mA accuracy 5 Note free wheelin...

Page 13: ...A 01 A_IN16 A A A A A A 06 05 04 03 02 01 CAN2_H CAN2_L CAN1_H CAN1_L GND VBBS P N1 Power supply CAN Bus 06 05 04 03 02 01 n c TEST RS 232 TxD RS 232 RxD GND VBBTEST N2 RS 232 Test X21 Outputs 14 13...

Page 14: ...only be carried out by the manufacturer The disposal must be carried out according to the corresponding national envi ronmental regulations 8 Approvals standards For test standards and regulations se...

Reviews: