31
UK
11.3.3 Setup “Transponder data block length”
Parameter
Description
Transponder data block
size
Block size in bytes of the RFID tag:
4/8/16/32/64/128/255
Please refer to the data sheet of the RFID tag for the block size
Only necessary for IO-channel mode “RWH_RW”
The value must be input as hexadecimal number .
Example: For 32 byte the setting shall be “20”
Select line 3 “PS CoE 0x4000:03” in tab “Startup” of the device . Enter the requested value .
11.3.4 Setup “Overload and Overcurrent detection”
With the parameter “Overload detection” the output current at terminal L+ can be controlled .
With the parameter “Overcurrent detection” the output current at terminal C/Qo can be controlled .
Parameter
Description
Overload detection
On: Overload on terminal L+ of the IO-port is supervised ( default )
The output current is limited to 500 . . .700 mA
Off: Supervision is off
The output current is not supervised and may increase up to 1200
mA . In this case the output driver of the IO-channel is protect against
overtemperature .
Overcurrent detection
On: Overcurrent on terminal C/Qo of the IO-port is supervised ( default )
The output current is limited to 500 mA
Off: Supervision is off
The output current is not supervised and may increase up to 600 mA . In this
case the output driver of the IO-channel is protect against overtemperature .
Select line 4 and 5 with “PS CoE 0x4000:04” and “PS CoE 0x4000:05” in tab “Startup” of the device .
Enter the requested value .
The maximum current consumption at terminal AUX + / AUX - may not exceed 3 A .
11.3.5 Setup “Read UID edge controlled”
If the UID of the RFID tag shall be read only when a “Read UID” command is started than the value shall
be set to “01” . (Activate synchronous mode)
If the UID of the RFID tag shall be read continuously without sending a command from the EtherCAT
master the value “00” shall be used . (Activate asynchronous mode)
Parameter valid only for IO-channel mode “RWH_RW”
Parameter
Description
UID edge controlled
Edge-controlled reading of the UID via bit RD in the control word of the
module RWH_RW
Default: Off
Select line 6 with “PS CoE 0x4000:06” in tab “Startup” of the device . Enter the requested value .
Repeat the setup for all used IO-channels .