DP1222
Converter 2 x 0...10 V / IO-Link
8
4.3.2 Window mode
SP2
SP2
SP2-H
H
OFF
SSC
SP1
SP1+H
SP1
H
ON
OFF
Fig. 5: NO (IO-Link parameter LoGc: high active)
SP1:
Switch-on point window
SP1+H: Switch-off point
SP2:
Switch-on point window
SP2-H:
Switch-off point
If the set voltage window is not complied with, this is signalled as “low” by a bit in the input process
data.
SP2
SP2
SP2-H
H
ON
SSC
SP1
SP1+H
SP1
H
OFF
ON
Fig. 6: NC (IO-Link parameter LoGc: low active)
SP1:
Switch-off point window
SP1+H: Switch-on point
SP2:
Switch-off point window
SP2-H:
Switch-on point
If the set voltage window is not complied with, this is signalled as “high” by a bit in the input process
data.
In operating mode 1, this function is not available.
4.3.3 Two point mode
SP2
SP1
SP2
H
OFF
ON
SSC
SP1
Fig. 7: NO (IO-Link parameter LoGc: no / high active)
SP1:
Trigger point overvoltage
SP2:
Switch-off point
If a set voltage is not reached, this is signalled as “low” by a bit in the input process data.
SP2
SP1
SP2
H
ON
SSC
SP1
OFF
Fig. 8: NC (IO-Link parameter LoGc: nc / low active)
SP1:
Trigger point undervoltage
SP2:
Switch-on point
If a set voltage is not reached, this is signalled as “high” by a bit in the input process data.
In operating mode 1, this function is not available.
4.3.4 Deactivated mode
NO (IO-Link parameter LoGc: high active)
The signal bit in the input process data is always signalled as “low”.
NC (IO-Link parameter LoGc: low active)
The signal bit in the input process data is always signalled as “high”.