5.1.2  Independent operation

No connection to the IO-Link master. If there is no connection to the IO-Link 

master when the operating voltage has been applied, the supply module transfers 

the parameter data to the connected circuit protection modules. The behaviour 

of the connected circuit protection modules is controlled via the configuration 

of the supply module. Either the status of the circuit protection modules is kept 

(FREEZE) or the circuit protection modules are switched off (UNFREEZE). If there 

is again connection to the IO-Link master and no fault occurred, the device goes 

to the "correct operation" mode.

5.1.3  Uncritical error

No valid configuration data is available. The connected circuit protection modules 

remain switched off. Cyclic data exchange is not possible, acyclic data exchange 

is conditionally possible. After the device has received the valid configuration and 

parameter data, it quits this operating mode.

5.1.4  Critical error

During initialisation an error is found or a critical error occurs. Communication with 

the IO-Link master is not possible. The connected circuit protection modules are 

and remain switched off.

 

► Reboot the device.

5.1.5  System start

The supply module is initialised when the operating voltage is applied. During this 

time communication with the IO-Link master is not possible.

5.2  DF22xx circuit protection modules

The different operating states of the circuit protection modules are indicated by 

LEDs.

off

missing operating voltage, 

error in initialisation or 

channel switched off via button

off

Green

on

channel switched on via button or IO-

Link, no error

on

Green/

orange

flashing

load current limit reached

on

Summary of Contents for DF21 Series

Page 1: ...Installation instructions Electronic circuit breakers IO Link for the 24 V DC secondary circuit DF21xx DF22xx 80278886 00 10 2018 UK...

Page 2: ...e matching circuit protection modules Observe the technical data of the circuit protection modules used The devices must be installed connected and put into operation by a qualified electrician Adhere...

Page 3: ...input and output current Insert wires directly into the terminals as shown on the device label Art no Terminals Potential Cross section mm Stripping length mm DF21xx 24 V DC supply 0 5 10 18 0 V 0 14...

Page 4: ...status LED channel 2 3 ON OFF reset button and status LED channel 1 4 push in terminals outputs 1 2 5 1 DF21xx supply modules Status LED Operating mode IO Link communication off missing operating vol...

Page 5: ...switched off Cyclic data exchange is not possible acyclic data exchange is conditionally possible After the device has received the valid configuration and parameter data it quits this operating mode...

Page 6: ...red once The status LED flashes orange to display the set nominal current The LED Flashes red once to confirm completion of the cycle The LED flashes orange once or multiple times in accordance with...

Page 7: ...ECClass2 Inputcurrent max totalcurrent A 40 Numberofchannels 1 2 NominalcurrentIN fail safeIN A 8 8 10 10 2 2 4 4 6 6 3 1 10 16 Mechanicaldata Installation Devicewidth mm Ambienttemperature C Storaget...

Page 8: ...ective circuit protection module and the respective wire cross sections 7 IO Link The load current warning threshold can be configured via the IO Link inter face to provide a visual warning and a warn...

Reviews: