6
Status LED
Operating status
Status of load output
Orange on
overload or short circuit until discon-
nection
on
Channel switched on via button and
switched off via IO-Link
off
Red
on
triggering via short circuit or overload
off
undervoltage in ON status with auto-
matic switching on again
5.3 Interrogation of module to confirm the set nominal current
Only for circuit protection modules with adjustable nominal current.
► Press the ON/OFF/reset button of the requested channel between 2 and 5
seconds.
> The status LED of the selected channel flashes red once.
> The status LED flashes orange to display the set nominal current. The LED
Flashes red once to confirm completion of the cycle. The LED flashes orange,
once or multiple times, in accordance with nominal current setting in amperes
(orange flashing once = 1 A; orange flashing twice = 2 A; etc.).
> The set nominal current is displayed five times. After 5 cycles the display
changes to the current operating status.To interrupt/stop the interrogation cycle,
and return to normal status indication mode, press the ON/OFF/reset button of
the requested channel at any time.
5.4 Setting of the nominal current
Only for circuit protection modules with adjustable nominal current.
► Set the nominal current via IO-Link using a corresponding parameter setting
software.