IO-Link master with EtherCAT interface DataLine 4 ports IP 65 / IP 66 / IP 67
56
>
9.2.14
IO-Link devices: Reading an writing device information
59797
Substructure:
iolinkmaster/port[n]/iolinkdevice
(n = 1...4)
Available data points:
Name
Description
Access
../status
Status of the connected IO-Link device
r
../vendorid
IO-Link ID of the vendor
r
../deviceid
IO-Link ID of the IO-Link device
r
../productname
Product name of the IO-Link device
r
../serial
Serial number of the IO-Link device
r
../applicationspecifictag
Device-specific identification (application tag)
rw
r ... read only
rw ... read and write
>
9.2.15
IO-Link devices: Indicating IO-Link events
59798
Substructure:
iolinkmaster/port[n]/iolinkdevice
(n = 1...4).
Available data points:
Name
Description
Access
../iolinkevent
Indication of IO-Link events
r
r ... read only
Subscribing events:
→
Subscribing to notifications
(
>
9.2.16
Gateway: Resetting, rebooting and localising the device
59790
Substructure:
firmware
Applicable services:
Name
Description
../factoryreset
Reset IO-Link master to factory settings
../reboot
Reboot IO-Link master
../signal
Trigger the flashing of the status LED