IO-Link master with EtherCAT interface DataLine 4 ports IP 65 / IP 66 / IP 67
25
9.1.1
Remarks
Content
Offline parameter setting ........................................................................................................................ 25
Fail-safe values of the IO-Link ports ....................................................................................................... 25
34180
>
Offline parameter setting
34060
The AL1330 supports the offline parameter setting. In this context, the user creates and stores a
configuration for the IO-Link master and the connected IO-Link devices without being connected to the
AL1330 (OFFLINE mode). The configuration created in this way can be stored as a file (*.lrp) and
loaded to the AL1330 and activated at a later date.
Further information about offline parameter setting:
→ Operating instructions LR DEVICE
>
Fail-safe values of the IO-Link ports
52521
The AL1330 has no failsafe function for the outputs of the IO-Link ports. If the fieldbus
connection is interrupted, the last used output values are written and marked as invalid.
>
9.1.2
IoT: Configure IP settings
34049
For access to the IO-Link master via the IT infrastructure the user has to set the IP settings of the IoT
port.
To configure the IP settings with DHCP, a DHCP server has to be active in the IT network. If
no DHCP server can be reached in the IT network, an IP address is automatically assigned to
the IoT port with the Zeroconfig protocol (address range:
→
Factory settings
(
To configure the IP settings of the IoT interface:
►
Select [IoT] menu.
>
The menu page shows the current settings.
►
Set the following parameters as required:
Name
Description
Possible values
[DHCP]
Activate/deactivate the DHCP client of the
device
[Static IP]
IP settings were set by the user
[DHCP]
IP settings are set by a DHCP
server in the network.
[IP address]*
IP address of the IoT port
Factory setting: 169.254.X.X
[Subnet mask]*
Subnet mask of the Ethernet network
Factory setting: 255.255.0.0
[Default gateway IP address]*
IP address of the network gateway
Factory setting: 0.0.0.0
[MAC address]
MAC address of the IoT port
The value is firmly set.
* ... can only be edited if parameter [DHCP] = [Static IP]
►
Save changed values on the device.
>