Command channels
>
Command response channel (device >>> fieldbus master)
11086
Offset
Word no.
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
2
reflected command number
3
reserved
Command status
(
4
command error code
>
Possible command error codes
11121
Error Code
Error
Description
0x00
no error
0x02
SND
no slave with the old address found
0x03
SD0
slave with address 0 connected
0x05
DE
error when deleting the old address
0x06
error when reading the extended ID code 1
0x07
SE
error when writing the new address or extended ID code 1
0x09
ET
extended ID code 1 could only be saved temporarily
0x0E
IA
invalid AS-i slave address 0 or 0B, or address 0 indicated twice
0x18
NM
master is not in the protected mode
0x21
invalid ID code 1 (if bit 3 is set for A/B slave)