4 Getting started
For fast set-up, the example configurations described in the following can be used
for most applications. The indicated minimum distances apply exclusively for each
separately described case.
4.1 Example configuration 1
Applied sensor:
LK1022 (probe length L = 264 mm)
Medium to be detected:
Mineral oil
Operating mode:
Manual media selection with overflow protection
(factory setting LK10xx)
→ 5.2.1
Type of installation:
Metal tank, installation to Fig.4-1
►
Install sensor.
►
Observe the distances (x), (u) and (c):
x:
min. 4.0 cm
u:
min. 1.0 cm
c:
max. 14.0 cm
►
Ground sensor and tank via an electrical
connection
(→ 7)
.
►
Observe the parameter setting sequence:
-[MEdI] = [OIL.2]
(→ 10.2.3)
-[OFS] = (u); e.g. (u) = 2.0 cm
(→ 5.2.4)
-[OP]: Set the overflow protection OP at a
distance (y) greater than 4.5 cm below the
mounting element.
For distances (y) smaller than 4.5 cm there
may be malfunctioning and error messages
during the adjustment process [cOP]
Fig. 4-1
OP
c
Step increment and setting range:
→ 12.2
Calculation aids for [OP]:
→ 12.3
►
Adjustment of the overflow protection OP to [cOP]
(→ 10.2.5)
>
The unit is ready for operation.
►
Make further settings if necessary.
►
Check whether the unit operates correctly.