The unit can be programmed before or after installation. Exception: to
adjust the overflow protection [cOP], the unit
must
be installed in the tank.
10.2 Basic settings
Setting ranges of all parameters:
→ 12
Factory settings of all parameters:
→ 14
10.2.1 Setting the unit of measurement [uni]
►
Enter [uni] before entering the values for SPx, rPx, OP or OFS.
This avoids unintentional maladjustments.
►
Select [uni]
►
Set the unit of measurement: [cm], [inch]
uni
10.2.2 Setting the offset [OFS]
The distance between tank bottom and lower edge of the measuring probe can be
entered as offset value
(→ 5.2.4)
.
►
Set [OFS] before entering the values for SPx, rPx or OP.
This avoids unintentional maladjustments.
►
Select [OFS].
►
Set the value for the offset. Note the set unit of measurement [uni].
OFS
10.2.3 Setting the medium [MEdI]
►
Select [MEdI] and set the corresponding sensitivity:
MEdI
[CLW.1] = water, hydrous media, coolant emulsions.
[CLW.2] = water-based media for temperatures > 35 °C (installation in
climatic tube).
[OIL.1] = oils with an increased DC value (e.g. some synthetic oils).
[OIL.2] = oils with a low DC value (e.g. mineral oils).
[Auto] =
automatic medium detection.
►
In case of doubt, select [OIL.2] for oils.
►
Proper functioning is to be ensured by carrying out an application test!