14
6.2 Installation instructions for operation without overflow
protection
[MEdI] = [Auto] or [OP] = [OFF] (Overflow protection OP deactivated!)
6.2.1 Installation in the inactive zone
Between the maximum level (b1) and the inactive zone (I1), minimum
distance (a1) must be adhered to (see Fig. 6-2 and Table 6-3)!
►
Fix the unit using mounting elements
in the inactive zone (I1). The extension
length (c) may not exceed (I1) (see
Table 6-3).
►
Make sure that the maximum level (b1)
is not exceeded after installation (see
Table 6-3).
►
Observe further minimum distances
according to Table 6-4.
Fig. 6-2
A
I1
c
I2
b1
a1
x
u
I1 / I2: Inactive zones
A: Active zone
a1: Minimum distance between the
inactive zone (I1) and the maximum
level (b)
b1: Max. level from the lower edge of the
sensor (without offset)
c: Max. permitted extension length
(Observe footnote Table 6-1)
Table 6-3
LKx022
LKx023
LKx024
[cm]
[inch]
[cm]
[inch]
[cm]
[inch]
I1
5.3
2.1
6.0
2.4
10.4
4.1
A
19.5
7.7
39.0
15.4
58.5
23.0
a1
1.0
0.4
1.5
0.6
2.5
1
b1
20.0
7.9
39.5
15.6
59.5
23.4