9 Technical information / Functioning / Parameters
9.1 Adjustable parameters
Switch-on point: Upper limit value at which the output changes its switching
status, indicated in cm or inch�
setting range
cm
inch
in steps of
LK0022 / LK7022
2�5 ��� 20�5
1�0 ��� 8�0
0�5 cm / 0�2 inch
LK0023 / LK7023
4�0 ��� 41�5
1�4 ��� 16�2
0�5 cm / 0�2 inch
LK0024 / LK7024
6�0 ��� 61�0
2�5 ��� 24�0
1�05 cm / 0�5 inch
Values for OFS = 0; with OFS > 0 the OFS value is added to these values�
Switch-off point: Lower limit value at which the output changes its switching
status, indicated in cm or inch�
setting range
cm
inch
in steps of
LK0022 / LK7022
2�0 ��� 20�0
0�8 ��� 7�8
0�5 cm / 0�2 inch
LK0023 / LK7023
3�5 ��� 41�0
1�2 ��� 16�0
0�5 cm / 0�2 inch
LK0024 / LK7024
5�0 ��� 60�0
2�0 ��� 23�5
1�05 cm / 0�5 inch
Values for OFS = 0; with OFS > 0 the OFS value is added to these values�
Dependence between rPx and SPx:
1� rPx is always lower than SPx� The unit only accepts values which are
lower than SPx�
2� If the difference between rPx and SPx is small (approx� 3 x steps),
increasing the switch-on point also increases the switch-off point (the
difference SPx - rPx remains constant)�
3� If the difference between rPx and SPx is great, rPx remains at the set
value even if SPx is increased�
4� If SPx is set to the minimum value and then increased, rPx is also set to
the minimum value and increased proportionally�
Switching functions of the transistor outputs:
4 settings can be selected:
-Hno = hysteresis / normally open
-Hnc = hysteresis / normally closed
-Fno = window function / normally open
-Fnc = window function / normally closed