Adjustable parameters
28
Technical information / Functioning / Parameters
Switch-on point 1 / 2
Upper limit value at which the output changes its switching
status.
SP2 is active only if
OU2
=
Hno
,
Hnc
,
Fno
or
Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching status.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is auto-
matically reduced (rPx is set to the minimum setting value).
rP2 is active only if
OU2
=
Hno
,
Hnc
,
Fno
or
Fnc.
Setting range for SPx
/
rPx
:
→
page 49.
Configuration of output 1
4 switching functions can be set:
-
Hno
= hysteresis / normally open
-
Hnc
= hysteresis / normally closed
-
Fno
= window function / normally open
-
Fnc
= window function / normally closed
Analogue start point
Measured value at which 4 mA / 0 V is provided.
ASP is active only if
OU2
=
I
or
U
.
Analogue end point
Measured value at which 20 mA / 10 V is provided.
Minimum distance between ASP and AEP = 25%
(scaling factor 4).
AEP is active only if
OU2
=
I
or
U.
Setting range for ASP
/
AEP
:
→
page 49.
Configuration of output 2
4 switching functions and 2 analogue signals can be set:
-
Hno
= hysteresis / normally open
-
Hnc
= hysteresis / normally closed
-
Fno
= window function / normally open
-
Fnc
= window function / normally closed
-
I
= analogue output 4 ... 20 mA
-
U
= analogue output 0 ... 10 V