8

Mounting of the Aseptoflex adapter

Step 1
Grease thread and sealing chamfer of 

the sensor and of the adapter with the 

greasing paste supplied
The greasing paste is food-grade 

(USDA-H1 84-201)
Make sure that the O-ring (D) is 

correctly positioned

D

1

1 = Grease

Step 2
Screw the sensor into the adapter 

Avoid mechanical influence on the 

sealing chamfers

Step 3
Clamp sensor and adapter into a 

clamping device (E) The sealing 

chamfers (F) must not be damaged
Tighten the sensor with a spanner until 

you can feel the end stop

E

F

36

If you continue to turn, this can have adverse effect on the sealing

Summary of Contents for Efector500 PF2058

Page 1: ...Operating instructions Electronic pressure sensor PF2058 704590 00 03 2009 UK ...

Page 2: ...ng elements 4 Function and features 5 Operating modes 6 Installation 7 Electrical connection 9 Programming 10 Installation and set up operation 11 Technical information Functioning Parameters 12 Adjustable parameters 12 Technical data 17 Scale drawing 18 Setting ranges 19 ...

Page 3: ...3 UK Menu structure RUN M S M M M S M M S M S M M S M M S M S M M S M S M S M M S M M S M M S M M S M M S M M S M RUN M M M M M M M S M M S M M S M M S M S S M OU2 Hno Hnc Fno Fnc OU2 I U ...

Page 4: ...cations check compliance of the product materials see Technical data with the media to be measured Controls and indicating elements 1 7 segment display Display of the system pressure display of parameters and parameter values 2 2 x LED red Switching status lights if output I II has switched 3 Mode Enter button Selection of the parameters and acknowledgement of the parameter values 4 Set button Set...

Page 5: ...ion N O Hno hysteresis function N C Hnc window function N O Fno window function N C Fnc Output polarity applies to both switching outputs p switching PnP n switching nPn Applications Type of pressure relative pressure Order no Measuring range Permissible overl pressure Bursting pressure PF2058 mbar 13 250 10 000 10 bar 30 000 30 bar inH2O 5 0 100 4 000 12 000 kPa 1 3 25 0 1 000 1 MPa 3 000 3MPa Av...

Page 6: ...unit continue as if in Run mode The parameter names are scrolled with each pressing of the Mode Enter button When the Set button is pressed briefly the corresponding parameter value is displayed for 15 s After another 15 s the unit returns to the Run mode Programming mode Setting of the parameter values While viewing a parameter value pressing the Set button for more than 5 s causes the unit to en...

Page 7: ...connection by means of a nut a clamping flange or similar B C A B A freely rotatable housing If it is not possible to slide the fixing element B down over the top of the sensor slide it up over the bottom of the sensor before the adapter is mounted NOTE A guarantee for a long term stable and maintenance free fitting with no bug traps in the hygienic sealing of the metal seal Aseptoflex connection ...

Page 8: ...ke sure that the O ring D is correctly positioned D 1 1 Grease Step 2 Screw the sensor into the adapter Avoid mechanical influence on the sealing chamfers Step 3 Clamp sensor and adapter into a clamping device E The sealing chamfers F must not be damaged Tighten the sensor with a spanner until you can feel the end stop E F 36 If you continue to turn this can have adverse effect on the sealing ...

Page 9: ...EN50178 SELV PELV Disconnect power before connecting the unit as follows 2 x p switching 2 x n switching L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 1 x p switching 1 x analogue 1 x n switching 1 x analogue L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 Connector view sensor Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue 4 B...

Page 10: ...play of the parameter value move to the maximum setting value Then the cycle starts again at the minimum setting value Select the display unit Uni before setting the switch points SPx rPx or the limits for the analogue output signal ASP AEP This avoids rounding errors generated internally during the conversion of the units and enables exact setting of the values If no button is pressed for 15 s du...

Page 11: ...r If viscous and residues producing media clog the filter cover of the sensor and thus reduce the measuring accuracy slightly you can clean it Unscrew the filter cover B use a pair of pliers with plastic covered jaws for this Clean the cover thoroughly The vent A should only be cleaned by skilled personnel and with utmost care A B Possible medium residues must not be compressed and pressed into th...

Page 12: ...Hno Hnc Fno or Fnc Setting range for SPx rPx page 19 Configuration of output 1 4 switching functions can be set Hno hysteresis normally open Hnc hysteresis normally closed Fno window function normally open Fnc window function normally closed Configuration of output 2 4 switching functions and 2 analogue signals can be set Hno hysteresis normally open Hnc hysteresis normally closed Fno window funct...

Page 13: ...0 1 of the value of the measuring range Calibration reset Resets the calibration set by COF to the value set at the factory Press the Mode Enter button until CAr is displayed Press the Set button and keep it pressed until is displayed Then press the Mode Enter button briefly Delay time for the switching outputs dSx switch on delay drx switch off delay The output does not immediately change its swi...

Page 14: ...very 200 ms d3 update of the measured value every 600 ms The update interval only refers to the display It has no effect on the outputs ph display of the measured peak value remains for a short time peak hold rd1 rd2 rd3 rph display as d1 d2 d3 Ph but rotated 180 OFF In the Run mode the display of the measured value is deactivated If one of the buttons is pressed the current measured value is disp...

Page 15: ...ion enables the monitoring of a defined acceptable range When the system pressure varies between the switch on point SPx and the switch off point rPx the output is switched window function NO or not switched window function NC The width of the window can be set by means of the difference between SPx and rPx SPx upper value rPx lower value 1 Fnc Fno Acceptable range 1 Scaling the measuring range an...

Page 16: ...e measuring range output signal 10 V Current output 4 20 mA Factory preset Measuring range scaled I mA P 4 20 MEW AEP 0 ASP 1 I mA P 4 20 AEP ASP 1 0 MEW I mA P 4 20 MEW AEP 0 ASP 1 I mA P 4 20 AEP ASP 1 0 MEW MEW final value of the measuring range The output signal is between 4 and 20 mA in the set measuring range It is also indicated System pressure above the measuring range output signal 20 mA ...

Page 17: ...Long time stability in of the span per year 0 1 Temperature coefficients TEMPCO in the compensated temperature range 0 80 C in of the span per 10 K Greatest TEMPCO of the zero point of the span 0 1 0 4 Materials wetted parts ceramics 99 9 Al2 O3 PTFE stainless steel 316L 1 4435 surface characteristics Ra 0 4 Rz 4 Housing material stainless steel 316L 1 4404 PBT Pocan PC Macrolon PEI EPDM X Santopr...

Page 18: ...18 Scale drawing 1 7 segment display 2 programming button 3 Aseptoflex sealing edge 4 Aseptoflex thread ...

Page 19: ...PF2058 mbar 11 250 12 249 13 188 50 250 1 Uni H2O SP1 SP2 rP1 rP2 ASP AEP P min max min max min max min max PF2058 inH2O 4 4 100 4 8 99 6 5 0 74 9 20 1 100 0 1 Uni PA SP1 SP2 rP1 rP2 ASP AEP P min max min max min max min max PF2058 kPa 1 1 25 0 1 2 24 9 1 3 18 8 5 0 25 0 0 1 P increments ...

Page 20: ...20 Set parameter values ...