10
Programming
1
Mode/Enter Set
Press the Mode/Enter button several
times until the respective parameter is
displayed
2
Mode/Enter Set
Press the Set button and keep it
pressed The current parameter value
flashes for 5 s, then the value is
increased* (incremental by pressing
briefly or scrolling by holding pressed)
3
Mode/Enter Set
Press the Mode/Enter button briefly
(= acknowledgement)
The parameter is displayed again, the
set parameter value becomes effective
4
Change more parameters:
Start again with step 1
Finish programming:
Wait for 15 s or press the Mode/Enter
button until the current measured value
is indicated again
*Decrease the value: Let the display of the parameter value move to the maximum setting
value Then the cycle starts again at the minimum setting value
Select the display unit (Uni) before setting the switch points (SPx, rPx) or the limits for the
analogue output signal (ASP, AEP) This avoids rounding errors generated internally during
the conversion of the units and enables exact setting of the values
If no button is pressed for 15 s during the setting procedure, the unit returns to the Run
mode with unchanged values
The unit can be electronically locked to prevent unwanted adjustment of the set
parameters: Press both pushbuttons for 10 s (the unit must be in Run mode)
Indication goes out briefly (acknowledgement of locking / unlocking)
Units are delivered from the factory in the unlocked state
With the unit in the locked state
is indicated briefly when you try to change
parameter values