Enhanced functions
This menu item contains a submenu with additional parameters
You can access these parameters by pressing the SET button briefly
Min-Max memory for system pressure
HI: displays the highest measured pressure
•
LO: displays the lowest measured pressure
•
Erase the memory:
Press the “Mode/Enter” button until HI or LO is displayed
-
Press the “Set” button and keep it pressed until “- - -” is displayed
-
Then press the “Mode/Enter” button briefly
-
Calibration offset
The internal measured value (operating value of the sensor) is offset
against the real measured value
Setting range: -5 +5% of the value of the measuring range (with scaling
•
as factory setting (ASP = 0% and AEP = 100%),
in steps of 01% of the value of the measuring range
•
Calibration reset
Resets the calibration set by COF to the value set at the factory
Press the “Mode/Enter” button until CAr is displayed
-
Press the “Set” button and keep it pressed until “- - -” is displayed
-
Then press the “Mode/Enter” button briefly
-
Delay time for the switching outputs
dSx = switch-on delay; drx = switch-off delay
The output does not immediately change its switching status when the
switching condition is met but when the delay time has elapsed If the
switching condition is no longer met when the delay time has elapsed, the
switching state of the output does not change
Setting range: 0 / 01 50 s adjustable in steps 01 s
•
(0 = delay time not active),
indicated in seconds
•
dS2 and dr2 are not active, if OU2 = I or U
Output polarity
2 options can be selected:
PnP = positive switching
-
nPn = negative switching
-
This setting applies to both switching outputs