background image

11

UK

8.3.1  Explanation min/max memory (MEM)

Lo�F

Minimum value of the flow measured in the process

Hi�F

Maximum value of the flow measured in the process

Lo�T

Minimum value of the temperature measured in the process

Hi�T

Maximum value of the temperature measured in the process

8.3.2    Explanation display function (DIS)

diS�L

Standard layout of the display(L1: flow or L2: flow and temperature)

diS�U

Update rate of display

diS�R

Display rotation 

diS�B

Display brightness

coL�F

Colour configuration volumetric flow

coL�T

Colour configuration temperature

OFF No colour change

rEd Process value always red

GrEn Process value always green

r-cF Display red if measured value between limit values cFL���cFH

G-cF Display green if measured value between limit values cFL���cFH

cFH�F

Upper limit value for colour change flow

Only if r-cF or 

G-cF is selected�

cFL�F

Lower limit value for colour change flow

cFH�T

Upper limit value for colour change temperature

cFL�T

Lower limit value for colour change temperature

9  Parameter setting

Parameters can be set before installation and set-up of the unit or during opera-

tion�

If you change parameters during operation, this will influence the function 

of the plant� 

 

► Ensure that there will be no malfunctions in your plant�

During parameter setting the unit remains in the operating mode� It continues to 

monitor with the existing parameter until the parameter setting has been complet-

ed�

Summary of Contents for efector 300 SV Series

Page 1: ...Operating instructions Vortex flow meter SVxxx4 80226711 00 06 2015 UK ...

Page 2: ... Main menu 8 8 1 1 Explanation main menu 8 8 2 Extended functions basic settings 9 8 2 1 Explanation basic settings CFG 9 8 3 Extended functions min max memory display 10 8 3 1 Explanation min max memory MEM 11 8 3 2 Explanation display function DIS 11 9 Parameter setting 11 9 1 Parameter setting in general 12 10 Troubleshooting 12 11 Factory setting 13 Technical data approvals accessories and fur...

Page 3: ...e to property can occur Improper or non intended use may lead to malfunctions of the unit or to un wanted effects in your application That is why installation electrical connec tion set up operation and maintenance of the unit must only be carried out by qualified personnel authorised by the machine operator In order to guarantee the correct condition of the device for the operating time it is nec...

Page 4: ...cts the two process categories volumetric flow and medium temperature Pressure Equipment Directive PED The units comply with the Pressure Equipment Directive and are designed and manufactured for group 2 fluids in accordance with the sound engi neering practice Use of group 1 fluids on request 4 Function The unit detects the volumetric flow quantity based on the Vortex measuring principle It featu...

Page 5: ...nlet and outlet side To do so provide for the following inlet and outlet pipe lengths F 1 2 DN nominal width of the pipe R radius Disturbance Inlet pipe length 1 Outlet pipe length 2 Non ideal bend 5 x DN 1 x DN Ideal bend R 1 8 x D N 0 5 x DN Multiple bends 2 x 90 15 x DN Reduction of internal pipe diameter 15 x DN 15 x DN Valve or pump 25 x DN Mount the unit in a way that no mechanical forces ar...

Page 6: ...ectrical connection The unit must be connected by a qualified electrician The national and international regulations for the installation of electrical equipment must be adhered to Voltage supply according to EN 50178 SELV PELV Disconnect power Connect the unit as follows 4 3 2 1 BK black BN brown BU blue WH white BN WH BK BU 4 1 3 2 OUT2 L L OUT1 Colours to DIN EN 60947 5 2 Pin 1 L Pin 3 L Pin 4 ...

Page 7: ... of the parameters and parameter values 4 Buttons and Select parameters Change parameter values hold button pressed Change of the process value display in the normal operating mode Run mode Locking unlocking press buttons simultaneously 10 seconds 5 Button Enter Change from RUN mode to the main menu Change to setting mode Acknowledgement of the set parameter value ...

Page 8: ...P1 ASP2 AEP2 EF 8 1 1 Explanation main menu ASP1 Analogue start value for temperature AEP1 Analogue end value for temperature ASP2 Analogue start value for volumetric flow AEP2 Analogue end value for volumetric flow EF Extended functions Opening of the lower menu level ...

Page 9: ...ctory settings Info Device information IO L Activate IO Link communication CFG Submenu basic settings MEM Submenu min max memory DIS Submenu display settings 8 2 1 Explanation basic settings CFG uni Standard unit of measurement for volumetric flow dAP Measured value damping in seconds only for volumetric flow FOU1 Behaviour of output OUT1 in case of an error FOU2 Behaviour of output OUT2 in case o...

Page 10: ...n 0 0 l min 0 0 C 0 0 C Hi F coL F OFF rEd r cF G cF GrEn cFH F cFL F cFH T cFL T diS L L1 L2 diS B diS U diS R d1 d2 d3 0 90 180 270 25 50 75 100 OFF coL T OFF rEd r cF G cF GrEn 10 l min 5 l min 50 C 0 C IO L Main menu For SVx6xx units gpm F The parameters are only displayed when selected r cF oder G cF ...

Page 11: ...rocess value always green r cF Display red if measured value between limit values cFL cFH G cF Display green if measured value between limit values cFL cFH cFH F Upper limit value for colour change flow Only if r cF or G cF is selected cFL F Lower limit value for colour change flow cFH T Upper limit value for colour change temperature cFL T Lower limit value for colour change temperature 9 Paramet...

Page 12: ...rA Error Parameter setting outside the valid range cr UL Error Measured value smaller than 30 critically low temperature cr OL Error Measured value greater than 130 critical excess flow temperature Locked via key Warning Setting pushbuttons on the unit locked parameter change rejected Locked via Communication Warning Parameter setting locked via pushbuttons parameter setting active via IO Link com...

Page 13: ...FOU2 FLOW OFF col F FLOW OFF col T TEMP OFF uni l min SVx6xx gpm dAP 0 6 s diS L L2 diS U d2 diS R 0 diS B 75 cFH F MEW cFL F MAW cFH T MEW cFL T MAW MEW final value of the measuring range MAW initial value of the measuring range The percentage values refer to the final value of the measuring range More information at www ifm com ...

Reviews: