71
ifm
Operating Instructions IO-Link Master with EtherNet/IP interface StandardLine 4 Ports IP 69K (AL1121)
2017-05-31
Appendix
>
Input assembly
11135
Byte
Content
0
Digital inputs of the IO-Link ports in the DI operating mode (
→
Mapping: digital input data (DI)
(
→ p.
1
2
Status information (
→
Mapping: Status information
(
→ p.
3
4...45
Acyclic command area: Response channel (
→
Response channel
(
→ p.
46...63
Port X01: Diagnostic, vendor ID, device ID, events (
→
Mapping: IO-Link port information
(
→ p.
64...81
Port X02: Diagnostic, vendor ID, device ID, results (
→
Mapping: IO-Link port information
(
→ p.
82...99
Port X03: Diagnostic, vendor ID, device ID, events (
→
Mapping: IO-Link port information
(
→ p.
100...117
Port X04: Diagnostic, vendor ID, device ID, events (
→
Mapping: IO-Link port information
(
→ p.
118
Port X01: Cyclic input data (n bytes)
118+n
Port X02: Cyclic input data (n bytes)
118+2n
Port X03: Cyclic input data (n bytes)
118+3n
Port X04: Cyclic input data (n bytes)
Legend:
n = [2,4,8,16,32]; is determined by the parameter [Prozess_Data_Length] (
→
Process data length
(
→ p.
>
Mapping: digital input data (DI)
23008
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
reserved
reserved
reserved
reserved
X04: Pin 4
X03: Pin 4
X02: Pin 4
X01: Pin 4
reserved
reserved
reserved
reserved
X04: Pin 2
X03: Pin 2
X02: Pin 2
X01: Pin 2
Legend:
X0n: Pin 4
Signal level on pin 4 of the
IO-Link port
1 bit
0x0 = OFF
0x1 = ON
X0n: Pin 2
Signal level on pin 2 of the
IO-Link port
1 bit
0x0 = OFF
0x1 = ON
Summary of Contents for AL1121
Page 108: ......