68
ifm
Operating Instructions IO-Link Master with EtherNet/IP interface StandardLine 4 Ports IP 69K (AL1121)
2017-05-31
Appendix
>
Communication profile
23072
name
Description
Possible values
[Communication
profile]
The access rights to the
parameter data, process data
and the events/diagnostic
messages of the IO-Link
master as well as the
connected IO-Link devices.
0x00
EtherNet/IP + LineRecorder
0x01
EtherNet/IP + LineRecorder (ro)
0x02
EtherNet/IP only
0x03
Continue in Use Case
>
Process data length
23016
Name
Description
Possible values
[Process data
length]
Length of the process input data and
process output data
Controller Tag: []
0x00
2 bytes input data, 2 bytes output data
Input assembly: 126 bytes
Output assembly: 54 bytes
0x01
4 bytes input data, 4 bytes output data
Input assembly: 134 bytes
Output assembly: 62 bytes
0x02
8 bytes input data, 8 bytes output data
Input assembly: 150 bytes
Output assembly: 78 bytes
0x03
16 bytes input data, 16 bytes output data
Input assembly: 182 bytes
Output assembly: 110 bytes
0x04
32 bytes input data, 32 bytes output data
Input assembly: 246 bytes
Output assembly: 172 bytes
Summary of Contents for AL1121
Page 108: ......