Installation of Product
p.24
2.2K Resistor Connection for Cut Off Check
You have to connect a 2.2K resistor between the input wire (e.g. Orange wire) and the GND
to apply the Cut Off Check feature. First, select whether or not to check the cutoff status of
each device from
[F5 SETUP MENU] -> CUT OFF SET
. Second, set the desired output that wil
l be generated in the event of a cutoff from
[F5 SETUP MENU] -> CUT OFF ALARM
.
4.3
Output Connection
Door Lock (Power Fail Safe) Connection (Door Relay)
1.
Connect COM wire of Door Relay (Gray wire with Red stripe) to +12V.
2.
Connect NC wire of Door Relay (Blue wire with White stripe) to (+) wire of Door Lock.
3.
Connect GND wire to (-) wire of Door Lock.
Door Lock (Power Fail Secure) Connection (Door Relay)
1.
Connect COM wire of Door Relay (Gray wire with Red stripe) to +12V.
2.
Connect NO wire of Door Relay (White wire with Red stripe) to (+) wire of Door Lock
3.
Connect GND wire to (-) wire of Door Lock.
Alarm Device Connection (Alarm Relay)
1.
Connect COM wire of Alarm Relay (White wire) to +12V.
2.
Connect NO wire of Alarm Relay (Purple wire) to (+) wire of Alarm device.
3.
Connect GND port to (-) wire of Alarm device.
Summary of Contents for LX007
Page 1: ......
Page 29: ...Installation of Product 8 p 21 1 Wall Mount Unit mm ...
Page 48: ...Setting Changes 12 p 40 ...
Page 49: ...p 41 F1 SETUP MENU 1 F1 SETUP MENU ...
Page 53: ...p 45 F2 SETUP MENU 2 F2 SETUP MENU ...
Page 91: ...p 83 F10 SETUP MENU 10 5 Module Version The version of the fingerprint module is displayed ...
Page 104: ...Troubleshooting p 96 If the problem persists please contact service center ...
Page 107: ...Index 99 ...