61
10. AC Input Voltage Setting
Warning: Do not set this parameter if your installation line voltage is 230 or 480 VAC.
If your AC line input voltage is 200-208 VAC or 318-400 VAC then you must set parameter number 01 to a
value of 2, indicating low line voltage to the AC drive. The AC drive needs this voltage calibration in order
to monitor bus voltages and motor current, ensuring protection of your pump motor.
1.
Starting from the main operational screen
S E T P T X X . X X X
F L O W
X X . X X X
2.
Press the MENU key
- M E N U -
C A L I B R A T I O N
3.
Press the UP arrow key
- M E N U -
S Y S T E M S E T U P
4.
Press the ENTER key
S Y S T E M S E T U P
S T A T U S
5.
Press the DOWN key
S Y S T E M S E T U P
T C F P A R A M E T E R S
6.
Press the ENTER key
P A R A M 0 1
V A L U E 1
7.
Press the ENTER key
P A R A M 0 1
V A L U E < 1 >
8.
Press the UP arrow key
P A R A M 0 1
V A L U E < 2 >
9.
Press the ENTER key
P A R A M 0 1
V A L U E 2
10.
Press the MENU key
T C F P A R A M E T E R S
A C T I V E
11.
Approximately 2 seconds
S Y S T E M S E T U P
T C F P A R A M E T E R S
Summary of Contents for Pulsafeeder MPC Vector
Page 6: ......
Page 43: ...37 This page is intentionally left blank...
Page 73: ...67 Continues next page...
Page 80: ...74 16 Menu Maps...
Page 81: ...75...
Page 82: ...76...
Page 83: ...77...
Page 84: ...78...
Page 85: ...79...
Page 86: ...80...
Page 87: ...81...
Page 88: ...82...
Page 89: ...83...
Page 90: ...84...
Page 91: ...85...
Page 92: ...86...
Page 93: ...87...
Page 94: ...88...
Page 95: ...89...
Page 96: ...90...
Page 97: ...91...
Page 105: ...99 Figure 8 Handheld Remote...
Page 112: ......
Page 113: ......
Page 114: ...and Keypad Functionality BULLETIN No IOM MPCVector UMPC 11 201010 Rv A...