48
MorphoWave Compact - 2018_2000035853-v81
The controller supports LED1 and LED2 signals
When the controller supports one relay contact for each of the possible answers then:
The « access granted » contact must be connected between the LED1 and the GND wires of the
terminal
The « access denied » contact must be connected between the LED2 and the GND wires of the
terminal.
The answer of the controller is "access granted", when the controller puts the LED1 wire to the low
state (by closing a contact between the LED1 and the GND wires),
and leaves the LED2 wire to the
high state.
The answer of the controller is "access denied", when the controller puts the LED2 wire to the low state
(by closing a contact between the LED2 and the GND wires),
whatever is the state of the LED1 wire.
terminal also considers that the answer of the controller is "access denied" in case of
time-out while expecting for a closure between LED1 and GND wires, or between LED2 and GND wires.
Summary of Contents for MorphoWave SP
Page 1: ...Copyright 2021 Idemia November 2021 2018_2000035853 v81 MorphoWave SP Installation guide ...
Page 2: ...Copyright 2021 Idemia November 2021 2018_2000035853 v81 ...
Page 7: ...7 MorphoWave Compact 2018_2000035853 v81 1 Introduction ...
Page 19: ...19 MorphoWave Compact 2018_2000035853 v81 2 General description ...
Page 27: ...27 MorphoWave Compact 2018_2000035853 v81 3 Installation procedure ...
Page 40: ...40 MorphoWave Compact 2018_2000035853 v81 4 Electrical interface ...
Page 57: ...57 MorphoWave Compact 2018_2000035853 v81 5 User interface ...
Page 61: ...61 MorphoWave Compact 2018_2000035853 v81 6 Recommendations ...
Page 65: ...65 MorphoWave Compact 2018_2000035853 v81 7 Annex 1 finger placement recommendations ...
Page 69: ...69 MorphoWave Compact 2018_2000035853 v81 8 Annex 2 Bibliography ...
Page 72: ...72 MorphoWave Compact 2018_2000035853 v81 9 Annex 3 Support ...