User Information

  

Safety Relays from IDEM           SEU-1 

H04 

Ver. A 

E61-326-00 

Maintenance 

The  device  must  be  checked  once  per  month  for  proper 
function  and  for  signs  of  tampering  and  bypassing  of  the 
safety function.

 

Techn. Data 

Corresponds to the standards 

EN 60204-

1; EN ISO 13849

-

1 ; EN 62061

 

Operating voltage 

 

AC 230 V, AC 115 V, AC/DC 24 V  

Rated supply frequency 

 

AC: 50-60 Hz 

Permissible deviation 

 

+ / - 10 % 

Power consumption 

 

DC 24 V 

AC 230 V 

 

 

approx. 1.2 W   approx. 3.5 VA 

Control voltage at S11 

 

DC 24 V 

Control current S11...S14 

 

max. 40 mA 

Safety contacts 

 

3 NO contacts 

Auxiliary contacts 

 

1 NC contact; monitoring contact for basic device

 

Max. switching voltage 

 

AC 250 V 

Safety contact breaking capacity  

AC:  

250 V, 1500 VA, 6 A for ohmic load 

 

 

 

250 V, 4 A for AC-15 

 

 

DC:  

24 V, 30 W, 1.25 A for ohmic load    

 

 

 

24 V, 30 W, 2 A for DC-13 

 

 

Max. total current through all 3 contacts: 10.5 A 

Minimum contact load  

 

24 V, 20 mA 

Min. Contact fuses 

 

6 A gG 

Max. line cross section 

 

0.14 - 2.5 mm

2

 

Max. length of control line 

 

1000 m with 0.75 mm

2

 

Contact material 

 

AgNi 

Contact service life 

 

mech. approx. 1 x 10

operating cycles 

Test voltage 

 

2.5 kV (control voltage/contacts) 

Rated impulse withstand voltage, leakage path/air gap 

4 kV 

(DIN VDE 0110-1) 

Rated insulation voltage 

 

250 V 

Degree of protection 

 

IP20 

Temperature range 

 

DC 24 V: 

  -15 °C to +60 °C 

 

 

AC 115 / 230 V:   -15 °C to +40 °C 

Degree of contamination 

 

(DIN VDE 0110-1) 

Overvoltage category 

 

(DIN VDE 0110-1) 

Weight  

 

approx. 230 g 

Mounting 

 

DIN rail according to EN 60715 TH35 

Note: 

Additional data can be requested from the manufacturer for 
applications that deviate from these conditions. 

Safety  
Characteristics  
According to 
EN ISO 13849-1 
 

The device is certified according to EN ISO 13849-1 up to a 
Performance Level of PL e. 

Device cannot be switched on again after an emergency 
stop:  

• 

Check whether the emergency stop circuit was closed 
again. 

• 

Was the start button opened before closing of the emer-
gency stop circuit (with manual start)? 

• 

Is the feedback loop closed? 

If the fault still exists, perform the steps listed under 
“Commissioning Procedure”. 

If these steps do not remedy the fault either, return the 
device to the manufacturer for examination. 

Opening the device is impermissible and will void the 
warranty.  

Device does not switch on: 

• 

Check the wiring of the SEU-1 and the basic device by 
comparing it with the wiring diagrams (also see user 
information for the basic device). 

• 

Check the safety switch used on the basic device for 
correct function and adjustment. 

• 

Check whether the emergency stop circuit of the basic 
device is closed. 

• 

Check whether the start button on the basic device (with 
manual start) is closed. 

• 

Check the operating voltage at A1 and A2 on the basic 
device and on the SEU-1. 

• 

Is the feedback loop closed? 

What to Do in  
Case of a Fault? 

The  device  is  otherwise  maintenance  free,  provided  that  it 
was installed properly.

 

Safety characteristics according to EN ISO 13849-1 for all variants of SEU-1 

Load (DC-

13; 24 V)

 

<= 0.1 A 

<= 1 A 

<= 2 A 

T10d [years] 

20 

20 

20 

Category 

PL 

PFHd [1/h] 

1.2E-08 

1.2E-08 

1.2E-08 

nop [cycle / year]  

<= 400,000 

<= 73,000 

<= 17,000 

Summary of Contents for SEU-1

Page 1: ...ed External fusing of the safety contacts 6 A gG must be provided A maximum length of the control lines of 1000 meters with a line cross section of 0 75 mm2 must not be ex ceeded The line cross section must not exceed 2 5 mm2 If the device does not function after commissioning it must be returned to the manufacturer unopened Open ing the device will void the warranty Installation As per EN 60204 1...

Page 2: ...d wiring space Category 4 PL e according to EN ISO 13849 1 is thereby possible If this fault cannot be ruled out category 3 PL e is achieved Applications Fig 3 Feedback Loop Contactors connected to the SEU 1 or the basic devices are monitored via the feed back loop of the basic device KA and KB are the positively driven contacts of the connected contactor or expansion module Wiring Feedback Loop F...

Page 3: ...ing DIN rail according to EN 60715 TH35 Note Additional data can be requested from the manufacturer for applications that deviate from these conditions Safety Characteristics According to EN ISO 13849 1 The device is certified according to EN ISO 13849 1 up to a Performance Level of PL e Device cannot be switched on again after an emergency stop Check whether the emergency stop circuit was closed ...

Page 4: ...ew terminals SEU 1 AC 230 V 50 60 Hz plug in terminals SEU 1 AC 115 V 50 60 Hz plug in terminals SEU 1 AC DC 24 V AC 50 60 Hz plug in terminals IDEM SAFETY SWITCHES Ltd 2 Ormside Close Hindley Industrial Estate Hindley Green Wigan WN2 4HR UK Tel 44 0 1942 261000 Fax 44 0 1942 676293 IDEM U S A 3909 Washington Blvd 204 Fremont CA 94538 email sales idemsafety com web www idemsafety com Feb 16 Fixed ...

Reviews: