Address Map
*1: Addresses generally used for Modbus communication. Calculation method of Modbus addresses for SmartAXIS devices are described below.
*2: These 4-digit addresses are used in the communication frame. To calculate the address used in communication frame, extract lower 5 digits of
the Modbus address, subtract 1 from the value, and convert the result into hexadecimal.
*3: Access within the device range for the SmartAXIS type used.
Calculating Modbus Addresses for SmartAXIS Devices
Modbus Device Name
Modbus Address
Map (Decimal)
*1
Communication
Frame Address
*2
SmartAXIS Device
*3
Applicable
Function Code
Coil
(000000 and above)
000001 - 000112
0000 - 006F
Q0 - Q141
1, 5, 15
000701 - 000828
02BC - 033B
R0 - R127
001001 - 002024
03E8 - 07E7
M0 - M1277
009001 - 009144
2328 - 23B7
M8000 - M8177
Input Relay
(100000 and above)
100001 - 100126
0000 - 007D
I0 - I155
2
101001 - 101200
03E8 - 04AF
T0 - T199 (timer contact)
101501 - 101700
05DC - 06A3
C0 - C199 (counter contact)
Input Register
(300000 and above)
300001 - 300200
0000 - 00C7
T0 - T199 (timer current value)
4
300501 - 300700
01F4 - 02BB
C0 - C199 (counter current value)
Holding Register
(400000 and above)
400001 - 402000
0000 - 07CF
D0 - D1999
3, 6, 16
408001 - 408200
1F40 - 2007
D8000 - D8199
409001 - 409200
2328 - 23EF
T0 - T199 (timer preset value)
3
409501 - 409700
251C - 25E3
C0 - C199 (counter preset value)
SmartAXIS Device
Calculating Modbus Address
Calculation Example
I, Q, M
Example: M325
(32 – 0)
8 + 5 + 1001 = 1262
Modbus address: 1262
1262 – 1 = 1261 = 04ED
Communication frame address: 04ED
R, T, C, D
Example: D756
(756 – 0) + 400001 = 400757
Modbus address: 400757
Extract lower 5 digits
757
757 – 1 = 756 = 02F4
Communication frame address: 02F4
Modbus Device Name
SmartAXIS Device
Minimum Address (4)
Offset (5)
Coil
Q0 - Q141
0
1
R0 - R127
0
701
M0 - M1277
0
1001
M8000 - M8177
8000
9001
Input Relay
I0 - I155
0
100001
T0 - T199 (timer contact)
0
101001
C0 - C199 (counter contact)
0
101501
Input Register
T0 - T199 (timer current value)
0
300001
C0 - C199 (counter current value)
0
300501
Holding Register
D0 - D1999
0
400001
D8000 - D8199
8000
408001
T0 - T199 (timer preset value)
0
409001
C0 - C199 (counter preset value)
0
409501
M XXX X
(2): Octal
(1): Decimal
(
(1)
–
(4)
)
8 +
(2)
+
(5)
Minimum
Offset
address
D XXXXX
(3): Decimal
(
(3)
–
(4)
) +
(5)
Minimum Offset
address
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......