2-4
●
Communication Functions
Serial
Standards
Compatible with the EIA RS232C standard
Baud Rate
9,600bps (Default) to 115,200bps
Synchro system
Asynchronous communication method
Transmission method
Full duplex
Ethernet
Standards
Compatible with the IEEE802.3 standard
Transmission rate
10BASE-T
100BASE-TX (Out of the standard coverage)
*1.Depending on the noise environments, Web Server Unit cannot communicate on the 100BASE-TX in
some cases.
*1
Communication protocol
IP/ICMP/ARP/TCP
*2.The number of unit to be connected at the same moment is one unit.
*2
/SMTP/HTTP/Telnet
●
Functions
Web Server
Supported Web Browser
Internet Explorer 6.0 or later
Netscape Navigator 7.2 or later
Java VM
Versions 1.42 or later
Alarms
Alarm contents
Alarm contents have to be registered in the Web Server Unit in advance.
The number of alarm types
32 types
Alarm character strings
Within 63 characters (1 byte character)
The number of destination
addresses
2 addresses (The sum of two address characters is up to 64 characters)
●
Connectable Unit
*1.The PLC requires the connecting cable type, FC4A-KC3C, to connect to the Web Server Unit.
PLC
*1
FC2A series
*2.Except for Micro
3
in FC2A series.
*2
, FC3A series, FC4A series
Programmable Display
*3,*4
*3.The programmable display requires the connecting cable type, HG9Z-3C125, to connect to the Web
Server Unit.
*4.The programmable display requires the firmware versions 1.8 or later.
*5.Please contact IDEC for more detail.