background image

15

Vanguard L  - 

Installation & Servicing 

GENERAL

9  SEALED (PRESSURISED) SYSTEM

Working pressure 6 bar maximum.

Particular reference should be made to BS 6644: Section 6 and 

Guidance note PM5 "automatically controlled steam and hot 

water boilers" published by the Health and Safety Executive.

The information and guidance given below is not intended to 

override any requirements of either of the above publications 

or the requirements of the local authority, gas or water 

undertakings.

In general commercial closed pressurised systems are 

provided with either manual or automatic water make up.

In both instances it will be necessary to fit automatic controls 

intended to protect the boiler, circulating system and ancillary 

equipment by shutting down the boiler plant if a potentially 

hazardous situation should arise.

Examples of such situations are low water level and operating 

pressure or excessive pressure within the system.

Depending on circumstances, controls will need to be either 

manual or automatic reset.

In the event of a shutdown both visual and audible alarms may 

be necessary.

Expansion vessels used must comply with BS. 4814 and must 

be sized on the basis of the total system volume and initial 

charge pressure.

Initial minimum charge pressure should not be less than 0.5 

bar (7.2 psi) and must take account of the static head and 

specification of the pressurising equipment.  The maximum 

water temperatures permissible at the point of minimum 

pressure in the system are specified in Guidance Note PM5.

When make up water is not provided automatically it will be 

necessary to fit controls which shut down the plant in the 

event of the maximum system pressure approaching to within 

0.5 bar (5 psi) of the safety valve setting.

Other British Standards applicable to commercial sealed 

systems are:

BS6880: Part 2

BS 1212

BS 6281: Part 1
BS 6282: Part 1
BS 6283: Part 4

10 VENTILATION

Safe, efficient and trouble-free operation of conventionally 

flued gas boilers is vitally dependent on the provision of an 

adequate supply of fresh air to the room in which the appliance 

is installed.

Ventilation by grilles communicating directly with the outside 

air is required at both high and low levels.  The minimum free 

areas of these grilles must be according to the following scale 

in Table below.

Ventilation Requirements

Required area (cm

2

) per kW of total rated input (net)

   

Boiler Room 

Enclosure

  Low level (inlet) 

10

  High level (outlet) 

5

Note.

Where a boiler installation is to operate in summer months 

(e.g. DHW) additional ventilation requirements are stated, if 

operating for more than 50% of time. (Refer to BS 6644)

Position ventilation grilles to avoid the risk of accidental 

obstruction by blockage or flooding.  If further guidance on 

ventilation is required then consult BS 6644.

The supply of air by mechanical means to a space housing 

the boiler should be by mechanical inlet with natural or 

mechanical extraction.  Mechanical extract ventilation with 

natural inlet must not be used.

Where a mechanical inlet and a mechanical extract system 

is applied, the design ventilation flow rates should be as in 

BS 6644.

Note.

For mechanical ventilation systems an automatic control 

should be provided to cause safety shutdown or lockout of 

the boiler(s) in the event of failure of air flow in either inlet 

or extract fans.

IMPORTANT.

 

The use of an extractor fan in the same 

room as the boiler (or in an adjacent communicating 

room) can, in certain conditions, adversely affect the safe 

operation of the boiler.

Where such a fan is already fitted (or if it is intended to 

fit an extractor fan after installation of the appliance) the 

advice of the gas supplier should be obtained.

Summary of Contents for Vanguard L 340

Page 1: ...ssured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature...

Page 2: ...80 DN100 DN100 DN100 DN125 DN125 DN125 DN150 DN150 DN175 DN175 Safety valve Expansion T3 Rp 2 Rp 2 Rp 2 Rp 2 DN65 DN65 DN65 DN80 DN80 DN100 DN100 Drain connection T4 in Rp 3 4 Rp 3 4 Rp 3 4 Rp 3 4 Rp...

Page 3: ...90 93 90 93 90 93 90 93 90 93 90 93 90 93 90 93 90 94 66 93 65 94 15 92 87 94 66 93 65 94 15 92 87 94 66 93 65 94 15 92 87 Hydraulic Resistance Max 15K mbar 20 6 33 3 27 5 47 1 35 3 60 8 53 82 4 53 83...

Page 4: ...upply 6 Hydraulic Resistance 2 3 Initial Start Up Lighting 34 Introduction 5 Installation 17 34 Performance Data 2 3 Positioning of the Turbulators 33 Servicing 35 36 Ventilation 15 Water Circulation...

Page 5: ...increased number of flue ways tubes which are positioned in the hottest area of the heat exchanger and constructed from a thicker steel construction than that of traditional boilers Burners The Vangu...

Page 6: ...N50081 1 EN50082 1 and EN55014 92 42 EEC Boiler Efficiency Directive 2009 142 EEC Gas Devices Directive Relevant standards are EN303 1 EN303 2 and EN304 IGE UP 1 Soundness testing and purging of indus...

Page 7: ...tank is used to fill the system with water and it is through the cold feed pipe that system water expands into the tank when the boiler passes heat into the system Conversely when the system cools wat...

Page 8: ...lve and expansion connection T4 Drain connection T5 Flue connection T6 Burner connection MODEL DIMENSION 340 420 510 630 A 860 890 890 890 B 1210 1275 1470 1780 C 1182 1352 1352 1352 D 190 190 190 190...

Page 9: ...ollector hood cleaning door 4 Flame inspection tube with pressure test nipple and cooling line connection Vanguard L 760 970 T1 Flow connection T2 Return connection T3 Safety valve and expansion conne...

Page 10: ...C 1432 1432 1542 1542 1702 1702 D 190 190 190 190 190 190 E 207 207 227 227 259 258 F 187 187 272 272 274 273 G 810 810 880 880 950 950 H 595 595 640 640 690 690 I 2346 2686 2781 3151 3225 3545 L 180...

Page 11: ...rner connection T7 Sludge hole T8 Handhole Vanguard L 3000 4000 MODEL DIMENSION 3000 3500 4000 A 1720 1970 1970 B 3230 3194 3594 C 1830 2090 2090 D 190 190 190 E 295 325 325 F 340 390 360 G 1315 1535...

Page 12: ...s requirements MODEL DIMENSION 4500 5000 5500 6000 6500 7000 A 2088 2088 2214 2214 2380 2380 B 226 226 240 240 240 240 C 2533 2533 2653 2653 2860 2860 D 417 417 437 437 509 509 E 445 445 465 465 595 5...

Page 13: ...air is required at both high and low levels Do not obstruct the grates of aspiration of the air or dissipation of the heat The boiler must be positioned so that there is enough space available for th...

Page 14: ...of the system 4 The boiler is at the highest point of the system Systems designed to rise above the flow connections will of course automatically require a minimum static head higher than shown 5 The...

Page 15: ...ng Other British Standards applicable to commercial sealed systems are BS6880 Part 2 BS 1212 BS 6281 Part 1 BS 6282 Part 1 BS 6283 Part 4 10 VENTILATION Safe efficient and trouble free operation of co...

Page 16: ...hall be inclined upwards at 45 11 FLUING Flue Size Refer to applicable regulations while determining the size and height of the flue Please note that Vanguard L boilers have pressurised and sealed com...

Page 17: ...the Upper Jacket 1 Body Insulation 1 1 1 Front Insulation 1 1 1 Rear Insulation 1 1 1 Central Body Insulation 1 1 1 Rear Side Jacket 2 2 2 Spare Parts Plastic Bag 1 1 1 Box Code VAL 07 10 10 10 17 17...

Page 18: ...25 2 DN125 2 DN125 2 DN150 2 DN150 2 DN175 2 DN175 2 DN200 2 DN200 2 DN200 2 DN200 2 DN250 2 DN250 2 DN250 2 DN250 2 DN250 2 DN250 2 DN250 Multiple Cable Clamp 4 4 4 4 4 4 4 4 4 4 4 4 4 Flange 1 DN65...

Page 19: ...nels 3 and 4 D Fit the rear insulation 6 fix the rear lower and upper retaining strips 7 and 8 with the self tapping screws Fit the plastic cable clamps 9 to the upper rear panel 8 E Fit the Ideal bad...

Page 20: ...3 4 van8103 18 POSITION OF THERMOMETER THERMOSTAT SENSOR IN THE BULB HOLDER Vanguard L 340 to 970 LEGEND 1 Thermometer bulb 2 Operation thermostat bulb 3 Safety thermostat bulb 4 Minimum temp thermost...

Page 21: ...r insulation 7 fix the rear lower panels 9 with pins and springs and the upper panel 10 with the self tapping screws 8 Fit the plastic cable clamps 11 to the upper rear panel 10 E Fit the Ideal badge...

Page 22: ...the plastic cable clamps 8 to it E Fit the Ideal badge to the front edge of the front top panel 9 and secure with the rubber fixings F Fit the control panel to front top panel 9 Remove the upper shell...

Page 23: ...front edge of the front top panel 8 and secure with the rubber fixings F Fit the control panel to front top panel 8 Remove the upper shell of the control panel and insert the capillaries of thermomete...

Page 24: ...ok them to the screws fitted to the upper square tube To determine which one of the front side panels is the left or the right ensure that the cable clamp plates 7 are positioned facing toward the fro...

Page 25: ...H L thermostat 3 Safety thermostat 4 Minimum thermostat Ensure that the sensors are inserted to the bottom of the bulb holder and then secure them with the retaining clip 5 In case some other thermost...

Page 26: ...ment panel pos 5 to the support pos 3 D After removal of the two side screws from the panel board rotate its cover towards the front and insert the cables and the capillaries of thermometer and thermo...

Page 27: ...mber can be achieved through adjustment of the screws 26 DOOR ASSEMBLY VANGUARD L 760 to 970 MODELS The combustion chamber door is fitted with four fixing points two on the left hand side which are no...

Page 28: ...when reversing the door the bushing 9 nut 10 and washer 11 will have to be moved as shown below details 1 and 3 for hinge side details 2 and 4 for hinge side Door Adjustment 1 Vertical door adjustmen...

Page 29: ...ied and must conform to the following directives and standards Gas Appliances Directive 90 396 CEE EN 267 Automating oil burners of monoblock type testing EN 676 Automatic forced draught burners for g...

Page 30: ...o it will be under power The switches 12 13 switch On and OFF the power to the burner and the Heating pump via a relay if necessary With the thermostat 21 the working temperature of the boiler can be...

Page 31: ...High temperature setting Live on this lead hence on T2 allows burner to fire on low fire in a 2 stage burner No 10 S3 Burner lockout indicator Feeds signal from lockout terminal on burner control box...

Page 32: ...FF Switch illuminated Position I ON Position OFF 12 Burner Switch Position I ON Position OFF 13 Pump Switch Position I I ON Position OFF 21 Boiler ON OFF High Low Thermostat High fire 54 C 84 C low fi...

Page 33: ...distance from the front tube plate as shown in the picture on the right When using the boiler at minimum output the smoke temperature will not be lower than 160 C In contrary case before get in touch...

Page 34: ...r and drain down to complete the flushing process c Refill and vent the system clear all air locks and again check for water soundness d Balance the system 3 Finally set the controls to the User s req...

Page 35: ...freezing Otherwise drain the system completely 42 SAFETY For boilers with gas burners It is the law that any service work must be carried out by a Gas Safe Registered Engineer WARNING Always turn off...

Page 36: ...es 4 Close off the fuel supply to the burner 5 Ensure that the boiler has been cooled to ambient temperature 6 Isolate the mains supply to the boiler and burner 7 Open the combustion chamber door afte...

Page 37: ...37 Vanguard L Installation Servicing NOTES...

Page 38: ...38 Vanguard L Installation Servicing NOTES...

Page 39: ...39 Vanguard L Installation Servicing NOTES...

Page 40: ...tinuing improvement in the design and performance of its products The right is therefore reserved to vary specification without notice The Ideal Boilers Technical Training Centre offers a series of fi...

Reviews: