1  BOILER CONTROLS / DISPLAY

In normal operation the display (C) shows the boiler status (see 

table above) and the water system flow temperature.

Blocking Mode

The boiler will enter blocking mode under certain fault 

conditions.  Whilst in blocking mode the burner is switched off.  

Once the fault conditions are clear the boiler will automatically 

reset itself.  In blocking mode the display will alternate between 

showing a '9' in digit one, along with the flow temperature in 

digits 2, 3 and 4, e.g.  

Followed by the blocking code 'bxx', e.g.  

Error Mode

In error mode the display will flash on and off with the error code 

shown, e.g.
The boiler will enter error mode under certain fault conditions.  

 9     9 6

 b     1 8

The unit will be inoperative until the fault is rectified.  The reset 

button is used to reset the boiler control module after an error 

has occurred.

Self Check and Anti-Seize Modes

After switching on the mains power or after a reset, the boiler 

performs a selfcheck, i.e. the DHW valve (if connected) is 

energised first for 15 seconds then the CH pump is switched on 

for a further 10 seconds.  This cycle repeats itself every 24hrs, 

as long as no heat request is given in 24hrs.

Burner on/off Switch

With the burner switch set to 'off' the boiler will not respond to a 

CH demand.  However, it will respond to a DHW demand and the 

pump anti-seize and frost protection modes are still operational 

any one of which could cause the boiler to fire.  Note. The burner 

switch is NOT a mains isolation switch.

CH/DHW Systems

In standby mode pressing and holding the '+' button for 3 

seconds turns the CH system on/off.
In standby mode pressing and holding the '-' button for 3 

seconds turns the DHW system on/off.

 E    3 6

A.

  Burner switch

B. 

Pressure gauge

C.

  Display

D.

  Reset button

E.

  Mode button

F.

  Step button

G.

  Store button

H.

  + button (to increase 

values)

I.

  - button (to decrease 

values)

Sequence  Boiler Status

 

DHW valve energised

 0 

Standby, no heat request

 1 

 Pre-purge, post purge

 

 2

 Ignition

 

3

 

Burner on in CH mode

 

4

 

Burner on in DHW mode

 

5

 

Waiting for air pressure switch to open or close

 

6

 

Burner off because a set value has been 

reached

  

7

 

Pump overrun in CH mode

  

8

 

Pump overrun in DHW mode

Operation

0

I

xtra

MODE

STEP

STORE

RESET

+

A

B

C

D

E

F

G

H

I

im8219

MASTER MODULE

CONTROL PANEL

3