31
-
Installation & Servicing
INSTALLATION
40 ADVANCED CONTROLS ACCESS CONT'D
Press
Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
. 0 0
. 5 9
14
15
Ignition fan speed (hundreds)
Do not
Do not
35
adjust
adjust
. 3 5
19
P19
CH post pump time (minutes)
01
99
05
Note 0 = 10 seconds
Do not set below 05
. 0 5
20
P20
DHW post pump time (x 10 seconds)
00
30
03
. 0 3
21
P21
P14
Maximum fan speed CH (units)
W45
00
W60
00
W80
Do not
Do not
00
W45P
adjust
adjust
00
W60P
00
W80P
00
P15
Maximum fan speed DHW (hundreds)
W45
55
W60
55
W80
Do not
Do not
59
W45P
adjust
adjust
50
W60P
49
W80P
57
. 0 0
16
P16
Maximum fan speed DHW (units)
W45
00
W60
00
W80
Do not
Do not
00
W45P
adjust
adjust
00
W60P
00
W80P
00
. 1 6
17
P17
Minimum fan speed (hundreds)
W45
18
W60
14
W80
Do not
Do not
16
W45P
adjust
adjust
17
W60P
13
W80P
15
. 0 0
18
P18
Minimum fan speed (units)
W45
50
W60
00
W80
Do not
Do not
00
W45P
adjust
adjust
00
W60P
00
W80P
00
CH modulation hysteresis on (ºC)
00
20
05
. 0 5
22
P22
CH modulation hysteresis off (ºC)
00
10
05
. 0 5
23
P23
DHW modulation hysteresis on (ºC)
-06
30
05
. 0 5
24
P24
DHW modulation hysteresis off (ºC)
-05
30
05
. 0 5
25
P25
INST
ALLA
TION
Summary of Contents for imax W45
Page 1: ......
Page 53: ...53 Installation Servicing NOTES...
Page 54: ...54 Installation Servicing NOTES...