Operating instructions
LEVEL
DESCRPTION
REGULATION
ENGLISH
According to version
ENG
CONTRAST
Adjust intensity of display
00
(-20) / (20)
DISPLAY SEL
Select additional display in standard operation
----
SELEC-PROG
Heating circuit 1 or Heating circuit 2
01
(01
-
02)
RETURN
1-DHW
If set the value 01 => the boiler switch on immediatly
00
(01
-
02)
T-DHW 1
Hot water temperature setting in first enable time
60
(10
-
70)
T-DHW 2
Hot water temperature setting in second enable time
60
(10
-
70)
T-DHW 3
Hot water temperature setting in third enable time
60
(10
-
70)
BOB VALUE
Operation without burner
(solar or solid fuel integration)
0
(0
-
70)
CIRCL-P-DHW
Ig set the value 01 => the circulation pump runs
when the hot water is enable, but the circulation
program is disabled
0
(0
-
1)
ANTILEGION
If the value 01 => every 20th time that heating
takes place or once per week on Saturday at
01:00 hrs the storage tank is heated up to 149 °F
0
(0
-
1)
RETURN
MODE
When setting an alternative oparating mode this
only applies to the assigned heating circuit
-----
T-ROOM DES 1
Room temperature setting in first enable time
20
(5
-
40)
T-ROOM DES 2
Room temperature setting in second enable time
20
(5
-
40)
T-ROOM DES 3
Room temperature setting in third enable time
20
(5
-
40)
T REDUCED
Required room temperature setting during night reduction
10
(5
-
40)
T-ABSENCE
Required room temperature setting during holidays
15
(5
-
40)
T-LIMIT DAY
Set the temperature value during heating time
19
(-5
-
40)
T-LIMIT N
Set the temperature value during reduction time
10
(-5
-
40)
HEATSLOPE
Set the Heatslope according to the installation
1,20 (0
-
3)
ADAPTION
Only active if an FBR analogue room device is
connected and an outdoor sensor
0
(0
-
1)
OPTIM HEAT
Activation of function for automatically bringing
forward the start of heating
10
(0
-
20)
ADAP ROOM-T
Room sensor adaptation
0
(5K
-
-5K)
OPTIM HEAT
Heating optimisation
0
(00
-
02)
MAX OPT-TIME
The start of heating is brought forward by no
more than this time
2
(00
-
03)
ECONO OPTI
Automatic reduction of burner disabling to the
end of set heating time
0
(00
-
02)
PC-ENABLE
Code number for enabling access to heating
circuit data from a PC (0000= access is blocked)
0000
(0000-9999)
RETURN
NOT USED
HOT WATER
HTG CIRCUIT 1/2
INSTALLATION
SOLAR / MF
Range
Set