13

Operating instructions

LEVEL

DESCRPTION

REGULATION

ENGLISH

According to version

ENG

CONTRAST

Adjust intensity of display

00

(-20) / (20)

DISPLAY SEL

Select additional display in standard operation

----

SELEC-PROG

Heating circuit 1 or Heating circuit 2

01

(01 

-

 02)

RETURN

1-DHW

If set the value 01 => the boiler switch on immediatly

00

(01 

-

 02)

T-DHW  1

Hot water temperature setting in first enable time

60

(10 

-

 70)

T-DHW  2

Hot water temperature setting in second enable time

60

(10 

-

 70)

T-DHW  3

Hot water temperature setting in third enable time

60

(10 

-

 70)

BOB VALUE

Operation without burner 

(solar or solid fuel integration)

0

(0 

-

 70)

CIRCL-P-DHW

Ig set the value 01 => the circulation pump runs
when the hot water is enable, but the circulation
program is disabled

0

(0 

-

 1)

ANTILEGION

If the value 01 => every 20th time that heating
takes place or once per week on Saturday at
01:00 hrs the storage tank is heated up to 149 °F

0

(0 

-

 1)

RETURN

MODE

When setting an alternative oparating mode this
 only applies to the assigned heating circuit

-----

T-ROOM DES  1

Room temperature setting in first enable time

20

(5 

-

 40)

T-ROOM DES  2

Room temperature setting in second enable time

20

(5 

-

 40)

T-ROOM DES  3

Room temperature setting in third enable time

20

(5 

-

 40)

T REDUCED

Required room temperature setting during night reduction

10

(5 

-

 40)

T-ABSENCE

Required room temperature setting during holidays

15

(5 

-

 40)

T-LIMIT DAY

Set the temperature value during heating time

19

(-5 

-

 40)

T-LIMIT N

Set the temperature value during reduction time

10

(-5 

-

 40)

HEATSLOPE

Set the Heatslope according to the installation

1,20 (0 

-

 3)

ADAPTION

Only active if an FBR analogue room device is
connected and an outdoor sensor

0

(0 

-

 1)

OPTIM HEAT

Activation of function for automatically bringing
forward the start of heating

10

(0

-

20)

ADAP ROOM-T

Room sensor adaptation

0

(5K

-

-5K)

OPTIM  HEAT

Heating optimisation

0

(00 

-

 02)

MAX OPT-TIME

The start of heating is brought forward by no
more than this time

2

(00 

-

 03)

ECONO OPTI

Automatic reduction of burner disabling to the
end of set heating time

0

(00 

-

 02)

PC-ENABLE

Code number for enabling access to heating
circuit data from a PC (0000= access is blocked)

0000

(0000-9999)

RETURN

NOT   USED

HOT WATER

HTG CIRCUIT 1/2

INSTALLATION

SOLAR / MF

Range

Set

AREAS USER

Summary of Contents for imax plus iii F95

Page 1: ...ing any part on this appliance use only spare parts that you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not bee...

Page 2: ...d utilizing today s heating technology and in compliance with the current safety regulations However following an improper use dangers could arise for the safety and life of the user or of other peopl...

Page 3: ...O BE HANDED OVER TO THE USER 5 SAFETY WARNINGS WARNING The installation adjustment and servicing of this appliance must be carried out by a competent person and installed in accordance with the curren...

Page 4: ...T I HEAT CIRCUIT II SOLAR MF Time programs CIRCL TIME HOTW PROGR HOTW PROGR I etc Expert INSTALLATION HOT WATER HEAT CIRCUIT I HEAT CIRCUIT II SOLAR MF INSTALLATION Change the parameter value with the...

Page 5: ...re shown the factory set parameters For additional information refer to the E8 instruction manual supplied with the boiler Press to enter Level ENGLISH Set new value TIME YEAR MONTH SETUP DAY 1 1 1 1...

Page 6: ...ART DAY STOP Press to return Open the flap DISPLAY GENERAL Elapsed 2 sec On display is shown the sub LEVEL Turn clockwise Turn clockwise Set new value Set new value Press to enter Level Press to enter...

Page 7: ...year XXXX MONTH START Set current holliday start month 01 12 DAY START Set current holliday start day 01 31 YEAR STOP Set current holliday end year XXXX MONTH STOP Set current holliday end year 12 31...

Page 8: ...T PRG 00 RETURN Press to exit OTHER PARAMETRES Open the flap Turn anticlokwise Elapsed 2 sec On display is shown the sub LEVEL Turn anticlokwise Press to enter Level Turn clockwise Turn clockwise Turn...

Page 9: ...it 1 F3 Upper buffer storage temperature F5 Flow temperature heating circuit 2 F6 Upper hot water temperature F8 Boiler Header temperature F9 Outside temperature F11 Flow temperature heating circuit 1...

Page 10: ...clockwise Turn clockwise Turn clockwise Press to enter Level Press to enter Level Press to enter Level Press to enter Level Turn clockwise Turn clockwise Turn clockwise Turn clockwise Turn clockwise T...

Page 11: ...DHW Hot water temperature value T DHW L Hot water temperature in infeed area T CIRC Recirculating temperature RETURN T ROOM DES A Current value for set room temperature T ROOM Room temperature HUMIDIT...

Page 12: ...to enter Level Set the value Turn clockwise Set the value Turn clockwise Set the value Turn clockwise Press to exit Turn clockwise Set the value Turn clockwise Set the value Turn clockwise Set the va...

Page 13: ...t T ROOM DES 1 Room temperature setting in first enable time 20 5 40 T ROOM DES 2 Room temperature setting in second enable time 20 5 40 T ROOM DES 3 Room temperature setting in third enable time 20 5...

Page 14: ...ating program for second controller heating circuit Active only with parameter 1 x HW 00 By leaving the hour blank_ _ _ _ the heating period is bypassed HTG PROG 1 Turn clockwise CIRCL TIME 1 HTG PROG...

Page 15: ...Set the value Turn clockwise Set the value Turn clockwise Set the value Press to exit Set the value Set the value Set the value Set the value Set the value Set the value Set the value Set the value S...

Page 16: ...el Set the Value Set the Value Set the Value Set the Value Set the Value Set the Value Turn clockwise Turn clockwise Turn clockwise Turn clockwise Turn clockwise Turn clockwise Turn clockwise Turn clo...

Page 17: ...Views the FA parameters of the boiler board module 7 Views the FA parameters of the boiler board module 8 Press to enter Level Turn clockwise Open the flap EXPERT HS Turn clockwise Turn clockwise Turn...

Page 18: ...in CAP MODULE After restarting the controller searches the bus systems 0 1000 NEW CONFIG If the BUS configuration was modified the automatic 00 01 MIN MOD CASC When the casacade is started the number...

Page 19: ...election 0 00 04 PUMP MODE Pump operating mode 02 00 03 MIXER OPEN Open mixer dynamic 18 5 25 MIXER CLOSE Close mixer dynamic 12 5 25 MAX T FLOW max flow temperature setting 80 20 110 MIN T FLOW min f...

Page 20: ...ert area Heating circuit I II HC FUNC 02 For additional informations refer to the E8 instruction manual supplied with the boiler Swimming pool temperature setting Only after function selection User Ar...

Page 21: ...E70 E8 F11 Flow temperature sensor heating circuit 1 E71 E8 F1 Lower storage temperature sensor Buffer E72 E8 F3 Higher storage temperature sensor Buffer E75 E8 F9 Outer temperature sensor AF E76 E8 F...

Page 22: ...USER 1X ACQUA C T AC 1 NOM T AC 2 NOM T AC 3 NOM MODE T ROOM DES 2 T ROOM DES 3 T REDUCED T ABSENCE T LIMIT DAY T LIMIT N HEAT SLOPE RETURN Compensation slope outer temperature SOLAR M F INSTAL Elapse...

Page 23: ...it is therefore necessary to always verify the boiler model on which it is use in order to select the most convenient setting Open the Flap Turn clockwise HTG PROG 1 CIRCL TIME 1 HTG PROG 2 1 HTG PRO...

Page 24: ...x 01482 448858 Registration No London 322 137 Ideal Stelrad Group pursues a policy of continuing improvement in the design and performance of its products The right is therefore reserved to vary speci...

Reviews: