9
Operating instructions
AREA
SERVICE
LEVEL
DESCRIPTION
TEST RELAYS Boiler in stand-by mode
RELAY TEST 00
No relay
RELAY TEST 01
A1:
Pump heating circuit 1
RELAY TEST 02
A2:
Pump heating circuit 2
RELAY TEST 03
A3:
Hot water charging pump
RELAY TEST 04
A4:
Mixer OPEN heating circuit 2
RELAY TEST 05
A5:
Mixer CLOSED heating circuit 2
RELAY TEST 06
A6:
Heat Source 1 ON
RELAY TEST 07
A7:
Heat Source 2 ON [2 stage: HS 1+2 (after 10s) ON]
RELAY TEST 08
A8:
Mixer OPEN heating circuit 1 / Multifunction 1
RELAY TEST 09
A9:
Mixer CLOSED heating circuit 1 / Multifunction 2
RELAY TEST 10
A10:
Multifunction 3
RELAY TEST 11
A11:
Collector pump / Multifunction 4
SENSOR TEST
F1
Buffer storage temperature Lower
F2
Buffer storage temperature Middle or room temperature heating circuit 1
F3
Upper buffer storage temperature
F5
Flow temperature heating circuit 2
F6
Upper hot water temperature
F8
Boiler/Header temperature
F9
Outside temperature
F11
Flow temperature heating circuit 1 or temperature multifunction 1
F12
Hot water temperature lower or temperature multifunction 2
F13
Solid fuel boiler temperature or collector 2 or temperature
multifunction 3
F14
Collector 1 temperature or temperature multifunction 4
F15
Room temperature heating circuit 2 or measured value of the ligth
sensor or voltage value 0-10V input
OTHER PARAMETERS
SW NO XXX-XX
Software number with index
CASCADE MANU
Starting different burner stages of the cascade
BURNER TIME
(1
-
8)
burner time for all stages
BURNER START
(1
-
8)
burner start for all stages
LIMITER TEST
(1
-
8)
Safety temperature limiter test: press the botton hold down
SERVICE
Date/Hour setting for service purposes
RESET USER
00
do not use
RESET EXPERT
00
do not use
RESET T-PRG
00
do not use
RETURN