27
xtra
-
Installation & Servicing
INSTALLATION
Press
Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
Booster time (minutes)
00
30
00
note 00 = Off
19
P19
CH flow parallel shift
00
80
10
For use with outside temperature sensor
20
P20
Tplus (
o
C)
Temperature added to DHW temperature set point (parameter 1)
00
30
20
when storage tank used.
21
P21
Maximum fan speed CH
(hundreds)
F80
48
F120
52
F160 Do not
Do not
51
F200 adjust
adjust
50
F240
53
F280
53
P22
30 ADVANCED CONTROLS ACCESS CONT'D
. 0 0
. 1 0
. 2 0
22
. 4 8
. 0 0
. 4 8
23
24
Ignition fan speed
(hundreds)
F80
35
F120
35
F160
Do not
Do not
35
F200
adjust
adjust
25
F240
25
F280
25
. 3 5
28
P28
P23
Maximum fan speed CH
(units)
F80
00
F120
50
F160
Do not
Do not
00
F200
adjust
adjust
00
F240
00
F280
00
P24
Maximum fan speed DHW
(hundreds)
F80
48
F120
52
F160
Do not
Do not
51
F200
adjust
adjust
50
F240
53
F280
53
. 0 0
25
P25
Maximum fan speed DHW
(units)
F80
00
F120
50
F160
Do not
Do not
00
F200
adjust
adjust
00
F240
00
F280
00
. 1 2
26
P26
Minimum fan speed
(hundreds)
F80
16
F120
13
F160
Do not
Do not
12
F200
adjust
adjust
13
F240
13
F280
12
. 1 6
27
P27
Minimum fan speed
(units)
F80
00
F120
50
F160
Do not
Do not
50
F200
adjust
adjust
50
F240
50
F280
50
continued...........
29
P29
Fan speed during forced low time
(x100 rpm)
F80
35
F120
16
F160
Do not
Do not
16
F200
adjust
adjust
16
F240
16
F280
16
. 1 6
INST
ALLA
TION