EXALT NATURAL GAS TO PROPANE CONVERSION INSTRUCTIONS

 

 

 

 

 

 

Table 1:  Combustion Settings

 

 

 

Propane 110, 155

 

Propane 199

 

Hi

gh

 Fi

re

 

CO

2

 Range

 

10.0 - 11.0%

 

CO

2

 Target

 

10.8%

 

O

2

 Range

 

5.7 - 4.2%

 

O

2

 Target

 

4.5%

 

CO Max

 

<200 ppm @ 10.8% CO

2

 

Lo

w

 Fi

re

 

CO

2

 Range

 

10.0 - 11.0%

 

CO

2

 Target

 

10.8%

 

10.4%

 

 

Target values are equivalent to High Fire values, ensure 

CO₂ values measured are less than or equal to High Fire 

CO₂ measurements

 

O

2

 Range

 

5.7 - 4.2%

 

O

2

 Target

 

4.5%

 

5.1%

 

 

Target values are equivalent to High Fire values, ensure 

O₂ values measured are higher than or equal to High Fire 

O₂ measurements

 

CO Max

 

10 ppm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Throttle Screw

 

Fig. 7:  Throttle Screw Location

 